2007-06-28 16:28:49 | |
| |
| *** UNSAT *** |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND |
| ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A |
| MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70(SHOWS A 2000 EDITION?) |
| |
| ** PLEASE SEE COMMENTS FROM FIRE AND OTHER TRADES FOR |
| OTHER CODES REFERENCED. |
| |
| 2) NOTE: PLEASE SEE THE PERMIT APPLICATION AS SUBMITTED |
| NEEDS TO CONTAIN THE SIGNATURES OF THE QUALIFIER OR |
| AUTHORIZED AGENT FOR THE ELECTRICAL CONTRACTOR. PLEASE |
| SEE THESE ALL APPEAR TO BE THE SAME SIGNATURE FROM THE |
| SAME PERSON. |
| PLEASE SEE THE NOTARY STATEMENT NEEDS TO BE FILLED OUT |
| CORRECTLY. PLEASE SUBMIT SIGNATURE VERIFICATION LETTERS |
| ORIGINAL AND NOTARIZED CORRECTLY UNDER FS 117.05. |
| ** PLEASE KNOW THE PERMIT APPLICATION AS SUBMITTED WILL |
| BE RETAINED BY THIS OFFICE. |
| |
| 3) NOTE: PLEASE SEE THE VALUE AS STATED ON APPLICATION |
| IS EXTREMELY LOW. PLEASE KNOW THE VALUE IS REQUIRED TO |
| BE FOR ALL LABOR, EQUIPMENT, CONSTRUCTION, MATERIALS, |
| DESIGN COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER |
| SUPPLIED. FBC 108.3 |
| ** PLEASE KNOW A VALUE MAY BE ASSESSED BY THIS OFFICE |
| IF AN APPROPRIATE VALUE IS NOT ADJUSTED. |
| |
| 4) NOTE: PLEASE KNOW THE EXISTING MTS AS STATED ON |
| PLANS MUST COMPLY WITH NEC 702.6. PLEASE KNOW THAT |
| THERE IS KEYED INTERLOCK EQUIPMENT WHICH DOES NOT MEET |
| THE NEC FOR INADVERTENT CONNECTION. |
| PLEASE KNOW MANY OF THESE DEVICES CONTAIN MULTIPLE KEYS |
| WHICH PERMIT THE DEVICES FROM BOTH POWER SOURCES BEING |
| TURNED ON AT THE SAME TIME. |
| PLEASE SUBMIT SPECS FOR EQUIPMENT TO BE SURE TO SUBMIT |
| THE SPECS FOR THE MTS TO VERIFY THIS IS NOT EQUIPMENT |
| AS STATED. |
| |
| 5) NOTE: PLEASE SEE RISER WHICH INDICATES ONLY ONE SET |
| OF CONDUCTORS RATED FOR 310AMPS FROM THE GENERATOR WHEN |
| THE BREAKER ON THE GENERATOR IS 600AMPS. |
| PLEASE SEE 240.4, 310.16 AND 445.13 |
| |
| 6) NOTE: PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS |
| NEED TO INDICATE THE OVER CURRENT PROTECTION OF THE |
| BREAKER TO COORDINATION WITH THE RISER. PLEASE ALSO BE |
| SURE THE SPECS/CUT SHEETS ALSO INDICATE THE MINIMUM |
| CLEARANCES FOR THE GENERATOR UNIT FROM ALL EQUIPMENT, |
| VENTS ETC. |
| PLEASE SEE THIS UNIT BEING DIESEL WILL REQUIRED A |
| MINIMUM OF 10FT FROM ANY OPENINGS INTO THE STRUCTURE. |
| PLEASE SEE MECHANICAL REVIEW FOR THIS. |
| FBC 106.1.2 FOR COORDINATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-06-28 15:25:02 | PLANS REMOVED FROM INCOMING AND IN ELEC FOR REVIEW. |
| PLANS ROUTED BACK TO INCOMING ONCE REVIEW IS DONE. |