Plan Review Notes
Plan Review Notes For Permit 07060491
Permit Number 07060491
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-28 16:28:49 
  
 *** UNSAT ***
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND
 ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70(SHOWS A 2000 EDITION?)
  
 ** PLEASE SEE COMMENTS FROM FIRE AND OTHER TRADES FOR
 OTHER CODES REFERENCED.
  
 2) NOTE: PLEASE SEE THE PERMIT APPLICATION AS SUBMITTED
 NEEDS TO CONTAIN THE SIGNATURES OF THE QUALIFIER OR
 AUTHORIZED AGENT FOR THE ELECTRICAL CONTRACTOR. PLEASE
 SEE THESE ALL APPEAR TO BE THE SAME SIGNATURE FROM THE
 SAME PERSON.
 PLEASE SEE THE NOTARY STATEMENT NEEDS TO BE FILLED OUT
 CORRECTLY. PLEASE SUBMIT SIGNATURE VERIFICATION LETTERS
 ORIGINAL AND NOTARIZED CORRECTLY UNDER FS 117.05.
 ** PLEASE KNOW THE PERMIT APPLICATION AS SUBMITTED WILL
 BE RETAINED BY THIS OFFICE.
  
 3) NOTE: PLEASE SEE THE VALUE AS STATED ON APPLICATION
 IS EXTREMELY LOW. PLEASE KNOW THE VALUE IS REQUIRED TO
 BE FOR ALL LABOR, EQUIPMENT, CONSTRUCTION, MATERIALS,
 DESIGN COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. FBC 108.3
 ** PLEASE KNOW A VALUE MAY BE ASSESSED BY THIS OFFICE
 IF AN APPROPRIATE VALUE IS NOT ADJUSTED.
  
 4) NOTE: PLEASE KNOW THE EXISTING MTS AS STATED ON
 PLANS MUST COMPLY WITH NEC 702.6. PLEASE KNOW THAT
 THERE IS KEYED INTERLOCK EQUIPMENT WHICH DOES NOT MEET
 THE NEC FOR INADVERTENT CONNECTION.
 PLEASE KNOW MANY OF THESE DEVICES CONTAIN MULTIPLE KEYS
 WHICH PERMIT THE DEVICES FROM BOTH POWER SOURCES BEING
 TURNED ON AT THE SAME TIME.
 PLEASE SUBMIT SPECS FOR EQUIPMENT TO BE SURE TO SUBMIT
 THE SPECS FOR THE MTS TO VERIFY THIS IS NOT EQUIPMENT
 AS STATED.
  
 5) NOTE: PLEASE SEE RISER WHICH INDICATES ONLY ONE SET
 OF CONDUCTORS RATED FOR 310AMPS FROM THE GENERATOR WHEN
 THE BREAKER ON THE GENERATOR IS 600AMPS.
 PLEASE SEE 240.4, 310.16 AND 445.13
  
 6) NOTE: PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS
 NEED TO INDICATE THE OVER CURRENT PROTECTION OF THE
 BREAKER TO COORDINATION WITH THE RISER. PLEASE ALSO BE
 SURE THE SPECS/CUT SHEETS ALSO INDICATE THE MINIMUM
 CLEARANCES FOR THE GENERATOR UNIT FROM ALL EQUIPMENT,
 VENTS ETC.
 PLEASE SEE THIS UNIT BEING DIESEL WILL REQUIRED A
 MINIMUM OF 10FT FROM ANY OPENINGS INTO THE STRUCTURE.
 PLEASE SEE MECHANICAL REVIEW FOR THIS.
 FBC 106.1.2 FOR COORDINATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-28 15:25:02PLANS REMOVED FROM INCOMING AND IN ELEC FOR REVIEW.
 PLANS ROUTED BACK TO INCOMING ONCE REVIEW IS DONE.