2007-07-11 19:01:12 | BUILDING PLAN REVIEW |
| PERMIT: 07060491 |
| ADD: 1554 PBL BLVD. |
| CONT: GREAT DANE PETROLEUM CONTRACTORS |
| TEL: (954)792-1334 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 1ST |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2)GENERATOR SLAB & ANCHOR REQUIREMENT |
| PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| PLUS PROVIDE PLANS WITH THE INFORMATION |
| DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| FASTENER, AND THE MINIMUM EDGE DISTANCE |
| THE DEVICE REQUIRES WITHOUT LOAD |
| REDUCTION. |
| SECOND, PROVIDE INFORMATION ON THE |
| SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| WIREMESH, FIBER MESH OR IF STEEL REBAR |
| WILL BE USED. |
| THE NEW SLAB AND HOLD DOWN DETAILS: |
| 104.2.1* ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 3)2004 FL. BLD CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO |
| INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| SITE WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST AND DESIGN FEES EXCLUDING LAND VALUE. OUR |
| VALUATION REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND |
| MEANS COST ANALYSIS SERVICES PER 108.3 FBC* |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |