2007-06-26 17:15:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)PLEASE REVISE CORNER FASTENING.SEE CALCULATIONS,
 HIGHLIGHTED (2" CENTER ROWS).THERE ARE SEVERAL MINOR
 ERRORS IN THE CALCULATIONS (OFF BY A FRACTION WHICH MAY
 AFFECT SOME JOBS BUT DOES NOT AFFECT THIS ONE), BUT ONE
 SIGNIFICANT APPARENT ERROR IS THAT THE "2" CENTER ROWS"
 STATES THAT THERE ARE 52 FASTENERS, BUT SHOULD BE
 DOUBLE THIS NUMBER.IN OTHER WORDS, IF THE SIDE LAP IS
 51 FASTENERS, 8" SPACING, THE TWO CENTER ROWS WOULD BE
 AT LEAST 102 FASTENERS WITH THE SAME SPACING.PLEASE
 CONTACT ME IF YOU NEED ASSISTANCE OR DISAGREE.