Plan Review Notes
Plan Review Notes For Permit 07060426
Permit Number 07060426
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-14 08:45:09****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX_1.)POLYPRO PRODUCT APPROVAL IS ILLEGIBLE.
  
 _XX_2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)CONTRACTOR HAS SUBMITTED SHINGLE AND TILE
 PRODUCT APPROVAL.IF BOTH ARE BEING INSTALLED, PROVIDE
 A ROOF PLAN SHOWING WHERE EACH TYPE OF ROOF WILL BE
 INSTALLED (FLAT, SHINGLE, TILE).
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT ARE REQUIRED.
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 _XX_ 7.)SEE PRODUCT LIMITATION #7 (FLAT DECK,
 POLYGLASS).CALCULATIONS PREPARED BY AN ARCHITECT,
 ENGINEER, OR REGISTERED ROOF CONSULTANT REQUIRED FOR
 ENHANCED FASTENING.