Plan Review Notes
Plan Review Notes For Permit 07060350
Permit Number 07060350
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-05 15:17:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)YOU'VE SUBMITTED COMPUTERIZED WIND LOADS FOR
 EXPOSURE C, BUT DID NOT CHANGE THE DESIGN PRESSURES ON
 THE INSTALLATION SCHEDULE.PLEASE REVISE.
  
 2.)SEE SHEET 14A OF THE PRODUCT APPROVAL.THE
 ANCHORING SPECIFIED IS FOR 3 1/2" EDGE DISTANCE.3"
 E.D. HAS A FACTOR OF .86.
  
 3.)THE SHUTTER SPAN COLUMN WAS LEFT BLANK.THIS
 SHOULD BE THE BLADE LENGTH, WHICH IS NOT THE SAME AS
 THE OPENING SIZE.PLEASE INCLUDE ALL REQUIRED
 INFORMATION.