2007-07-05 15:17:38 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.)YOU'VE SUBMITTED COMPUTERIZED WIND LOADS FOR | | EXPOSURE C, BUT DID NOT CHANGE THE DESIGN PRESSURES ON | | THE INSTALLATION SCHEDULE.PLEASE REVISE. | | | | 2.)SEE SHEET 14A OF THE PRODUCT APPROVAL.THE | | ANCHORING SPECIFIED IS FOR 3 1/2" EDGE DISTANCE.3" | | E.D. HAS A FACTOR OF .86. | | | | 3.)THE SHUTTER SPAN COLUMN WAS LEFT BLANK.THIS | | SHOULD BE THE BLADE LENGTH, WHICH IS NOT THE SAME AS | | THE OPENING SIZE.PLEASE INCLUDE ALL REQUIRED | | INFORMATION. |
|