2007-09-12 14:32:26RESIDENTIAL STRUCTURAL REPAIRS BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND
 2004 FBC 2004 WITH 2007 REVISIONS.
  
 1- NEW WALL AREA ON UNIT #2 NEED TO HAVE BEDROOM #1
 WINDOW THAT COMPLIES WITH EGRESS REQUIREMENTS OF SEC.
 R310.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.NEW SINGLE
 HUNG WINDOW 37" X 50" SPECIFIED ON PLANS DOESN'T
 PROVIDE THE 24" MIN. CLEAR HEIGHT OPENING.REVISE
 WINDOW SIZE OR PROVIDE WINDOW CUT SHEETS SHOWING HOW
 THIS WINDOW SIZE PROVIDE THE MIN. CLEARANCE.
  
 2- PROVIDE ENLARGED DETAIL/SECTION SHOWING HOW SIMPSON
 HETAL 20CONNECTOR IS GOING TO BE INSTALLED OVER
 EXISTING 2" X 8" ROOF JOIST IF ROOF IS NOT GOING TO BE
 REMOVED. SEE TRUSS CATALOG FOR PROPER CONNECTOR
 INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 3- TYP. WALL& BEAM ATTACHMENT DETAIL SPECIFIES #4
 BARS AT CORNERS WHILE BEAM IS REINFORCED WITH #5 BARS.
 PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING
 STRUCTURAL INTEGRITY AND CONTINUITY OF REINFORCEMENT
 WHEN USING DIFFERENT SIZE OF BARS.SEC. 106.1.2 CITY
 AMENDMENTS AND SEE ACI 318-02 SEC. 7.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)8057612