Plan Review Notes For Permit 07060347 |
Permit Number |
07060347 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-20 16:37:42 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO | | ELECTRICAL WORK IN THE DESCRIPTION ON THE APPLICATION | | AND NO CONTRACTOR SIGNED ON. INDICATE WHAT IS NEW AND | | WHAT IS EXISTING.IF NEW ELECTRICAL IS TO BE INSTALLED | | AN ELECTRICAL PERMIT WILL BE REQUIRED . | | | | 2} PROVIDE A PANEL SCHEDULE TO INCLUDE NEW WORK. | | INDICATE AMPERAGE, OCP AND WIRE SIZE. SEE 408.4 CIRCUIT | | DIRECTORY. | | | | 3} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON | | PLANS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|