Plan Review Notes For Permit 07060328 |
Permit Number |
07060328 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-25 12:17:37 | *****UNSAT***** | | | | | | 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO | | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF 7.2.1.6.2 | | NFPA 101 (2003 EDITION) BE MET. | | | | 2.ACCORDING TO SUBMITTED APPLICATION'S PROJECT | | DESCRIPTION, 21 READERS AND 21 DOOR STRIKES WERE | | DETAILED.THE SUBMITTED PLAN SHEETS, HOWEVER SHOW ONLY | | 18 DOOR STRIKES.THREE (3) DOOR STRIKES (DS) APPEAR TO | | BE MISSING FROM THE MEZZANINE FLOOR PLAN. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|