Plan Review Notes For Permit 07060314 |
Permit Number |
07060314 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-08-30 17:35:29 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY | | OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY | | | | FROM PREVIOUS LIST: | | | | | | 1.ENGINEER'S SIGNATURE IS TO BE ORIGINAL. | | ENGINEERING IS OPTIONAL FOR BUILDINGS UNDER 60'. | | | | NEW COMMENTS: | | | | 2.)ENGINEERING IS BASED ON ASCE7-98, CORRECT VERSION | | IS ASCE7-02, FBC35. | | | | 3.)TWO SETS OF PERMIT DOCUMENTS REQUIRED.ONLY ONE | | INSTALLATION SCHEDULE WAS PROVIDED.DUE TO WORK LOAD, | | I CANNOT MAKE COPIES FOR CONTRACTORS.THERE IS A | | PHOTOCOPY MACHINE IN THE LOBBY FOR THIS PURPOSE. | | | | 4.)SHUTTER MOUNTING CONNECTION TYPE SHOULD BE A | | THROUGH L, SEE SHEETS 10-11 OF THE PRODUCT APPROVAL. | | | | 5.)2/1/2 INCH EDGE DISTANCE WAS SPECIFIED.SEE SHEET | | 11, THIS REQUIRES A FACTOR FOR ANCHOR SPACING. | | | | 6.)THE ANCHOR YOU CHOSE IS NOT ONE OF THE THREE | | INCLUDED IN THE PRODUCT APPROVAL.EITHER SELECT ONE | | FROM THE PRODUCT APPROVAL OR PROVIDE ENGINEERING. | | | | |
|