Plan Review Notes
Plan Review Notes For Permit 07060314
Permit Number 07060314
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-30 17:35:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST:
  
  
 1.ENGINEER'S SIGNATURE IS TO BE ORIGINAL.
 ENGINEERING IS OPTIONAL FOR BUILDINGS UNDER 60'.
  
 NEW COMMENTS:
  
 2.)ENGINEERING IS BASED ON ASCE7-98, CORRECT VERSION
 IS ASCE7-02, FBC35.
  
 3.)TWO SETS OF PERMIT DOCUMENTS REQUIRED.ONLY ONE
 INSTALLATION SCHEDULE WAS PROVIDED.DUE TO WORK LOAD,
 I CANNOT MAKE COPIES FOR CONTRACTORS.THERE IS A
 PHOTOCOPY MACHINE IN THE LOBBY FOR THIS PURPOSE.
  
 4.)SHUTTER MOUNTING CONNECTION TYPE SHOULD BE A
 THROUGH L, SEE SHEETS 10-11 OF THE PRODUCT APPROVAL.
  
 5.)2/1/2 INCH EDGE DISTANCE WAS SPECIFIED.SEE SHEET
 11, THIS REQUIRES A FACTOR FOR ANCHOR SPACING.
  
 6.)THE ANCHOR YOU CHOSE IS NOT ONE OF THE THREE
 INCLUDED IN THE PRODUCT APPROVAL.EITHER SELECT ONE
 FROM THE PRODUCT APPROVAL OR PROVIDE ENGINEERING.
  
  