2007-10-17 10:25:35 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) ENERGY CALCULATIONS LINE 15 IS TAKING A CREDIT FOR |
| HF-WHOLE HOUSE FAN, PER 2004 FBC 13-607.1.A.3.2 THIS |
| BUILDING DOES NOT QUALIFY FOR THAT CREDIT. PLEASE |
| CORRECT. |
| *** SEE SUBCHAPTER 13-2 DEFINITIONS WHOLE - HOUSE FAN . |
| A MECHANICAL VENTILATION SYSTEM USUALLY INSTALLED IN |
| THE CEILING OF A RESIDENCE WHICH IS USED TO EXHAUST AIR |
| FROM THE INTERIOR OF A BUILDING TO AN ATTIC SPACE WITH |
| SUFFICIENT VENTING AREA TO TRANSFER THE AIR TO THE |
| OUTSIDE. |
| ***13-607.1.A.3.2 WHOLE HOUSE FAN CREDIT. |
| HOUSES FOR WHICH WHOLE HOUSE FAN CREDIT IS CLAIMED |
| SHALL HAVE INSTALLED A WHOLE HOUSE FAN SIZED TO PROVIDE |
| A MINIMUM OF 20 AIR CHANGES PER HOUR FOR THE ENTIRE |
| HOUSE. THE FAN INSTALLED SHALL HAVE A FREE AIR CFM |
| RATING OF AT LEAST THREE TIMES THE SQUARE FOOTAGE OF |
| THE CONDITIONED AREA OF THE HOUSE. TO ENSURE ADEQUATE |
| AIR EXHAUST, THE HOUSE ATTIC SHALL HAVE GABLE, RIDGE OR |
| WIND TURBINE VENTS WHOSE TOTAL OPENING AREA IS EQUAL TO |
| FOUR TIMES THE CEILING CUTOUT AREA FOR THE WHOLE HOUSE |
| FAN. SOFFIT VENTS SHALL NOT BE INCLUDED IN THE EXHAUST |
| VENT AREA. |
| |
| 2) PLEASE SHOW THE SIZE OF THE RETURN AIR GRILL TO THE |
| AIR HANDLER, SEE W.P.B 106.3.5.4 (10). |
| |