2007-10-17 10:25:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 15 IS TAKING A CREDIT FOR
 HF-WHOLE HOUSE FAN, PER 2004 FBC 13-607.1.A.3.2 THIS
 BUILDING DOES NOT QUALIFY FOR THAT CREDIT. PLEASE
 CORRECT.
 *** SEE SUBCHAPTER 13-2 DEFINITIONS WHOLE - HOUSE FAN .
 A MECHANICAL VENTILATION SYSTEM USUALLY INSTALLED IN
 THE CEILING OF A RESIDENCE WHICH IS USED TO EXHAUST AIR
 FROM THE INTERIOR OF A BUILDING TO AN ATTIC SPACE WITH
 SUFFICIENT VENTING AREA TO TRANSFER THE AIR TO THE
 OUTSIDE.
 ***13-607.1.A.3.2 WHOLE HOUSE FAN CREDIT.
 HOUSES FOR WHICH WHOLE HOUSE FAN CREDIT IS CLAIMED
 SHALL HAVE INSTALLED A WHOLE HOUSE FAN SIZED TO PROVIDE
 A MINIMUM OF 20 AIR CHANGES PER HOUR FOR THE ENTIRE
 HOUSE. THE FAN INSTALLED SHALL HAVE A FREE AIR CFM
 RATING OF AT LEAST THREE TIMES THE SQUARE FOOTAGE OF
 THE CONDITIONED AREA OF THE HOUSE. TO ENSURE ADEQUATE
 AIR EXHAUST, THE HOUSE ATTIC SHALL HAVE GABLE, RIDGE OR
 WIND TURBINE VENTS WHOSE TOTAL OPENING AREA IS EQUAL TO
 FOUR TIMES THE CEILING CUTOUT AREA FOR THE WHOLE HOUSE
 FAN. SOFFIT VENTS SHALL NOT BE INCLUDED IN THE EXHAUST
 VENT AREA.
  
 2) PLEASE SHOW THE SIZE OF THE RETURN AIR GRILL TO THE
 AIR HANDLER, SEE W.P.B 106.3.5.4 (10).
  