2007-10-26 17:00:16 | NEW SINGLE FAMILY RESIDENCE BUILDING REVIEW THIRD |
| CHECKLIST. |
| REVIEW UNDER FLORIDA RESIDENTIAL CODE 2004 AND FBC 2004 |
| WITH 2006 REVISIONS. |
| |
| 1- NEED TO GET APPROVAL FROM ZONING. SEE ZONING |
| COMMENTS. |
| |
| 2- SHEET 3.1 SPECIFIES CONSTRUCTION TYPE III.SPECIFY |
| WHAT TYPE III.A OR B?.ALSO,BE AWARE THAT TYPE III |
| CONSTRUCTION REQUIRES A TWO HOUR FIRE RATED WALL. SEE |
| TABLE 601 AND TABLE 602 OF FBC 2004. NEED TO SPECIFY |
| HOW ACHIEVING THE 2 HOUR FIRE RATING REQUIRED BY TABLES |
| 601 AND 602 FBC 2004. |
| |
| 3- PROVIDE COMPLETE MANUFACTURER SPECS FOR 2 HOUR |
| CONCRETE BLOCK AS REQUIRED BY ITEM 2 ABOVE. |
| |
| 4- RE-SUBMITTAL FEEOF $193.10 WAS NOT PAID AT TIME OF |
| SUBMITTAL.IN ADDITION, NEW RE-SUBMITTAL FEEWILL BE |
| DUE AT TIME OF RE-SUBMITTAL. |
| |
| 5- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004 |
| FLORIDA RESIDENTIAL CODE.(REPEAT COMMENT). |
| |
| 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| ***NOTE: REMEMBER THAT ENGINEER OF RECORD NEEDS TO |
| REVIEW AND APPROVE ALL PRODUCT APPROVALS IN WRITING |
| (NOT SIGNING AND SEALING) PRIOR TO SUBMITTAL TO THIS |
| OFFICE. |
| |
| A) PRECAST LINTELS. PROVIDE CURRENT FLORIDA PRODUCT |
| APPROVAL REPORT FL158-R2. THIS IS THE ONE THAT |
| REFERENCES NOA 06-0222.01 SUBMITTED.ONE SUBMITTED IS |
| FL158-R1 WHICH IS THE OLD ONE AND WAS REVISED. |
| |
| B) SINGLE HUNG WINDOWS. PROVIDE CURRENT FLORIDA |
| PRODUCT APPROVAL REPORT FL239-R10 AND CORRESPONDING |
| NOA.FL239-R4 IS OLD AND WAS REVISED. |
| |
| 7- STORM SHUTTERS: |
| A) INSTALLATION SCHEDULE SUBMITTED SHOWS 12.5" |
| ANCHOR SPACING. LOOK AT STORM PANEL DETAIL #1 ON SHEET |
| 1 OF 6 OF STORM SHUTTERS DRAWINGS AND REVISE AS |
| REQUIRED. |
| |
| B) REVISE MINIMUM PANEL LENGTH FOR THE FOLLOWING |
| OPENINGS: #1, #3, #5 AND #8.SEE TABLE 2 ON PAGE 6 OF |
| 6 OF SHUTTERS DRAWINGS SUBMITTED. |
| |
| C) CLEARLY SPECIFYSHUTTER MOUNTING CONDITION ON |
| THE 4TH COLUMN OF STORM SHUTTER INSTALLATIONSCHEDULE. |
| EG:NEED TO SPECIFYIFWALL MOUNTED OR BUILT OUT, |
| ETC.TO VERIFY COMPLIANCE WITH WIND LOADS SEC. 1609 |
| FBC 2004.(REPEAT COMMENT). |
| |
| D) PROVIDE KEY PLAN TO IDENTIFY OPENING LOCATION TO |
| VERIFY COMPLIANCE WITH WIND LOADS SEC. 1609 FBC 2004. |
| (REPEAT COMMENT). |
| |
| 8- ROOF DESIGN LOADS ON SHEET 5.1 IS MISSING THE ATTIC |
| LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| 9- A) SURVEY SUBMITTED NEEDS THE SURVEYOR ORIGINAL |
| SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE. |
| |
| B) SURVEY TO HAVE COMPLETE ADDRESS NUMBER. |
| |
| 10- TRUSS PACKAGE: |
| A) ENGINEER TO PROVIDE ORIGINAL SIGNATURE, NOT |
| RUBBER STAMP SIGNATURE.SEC. 61G15-23.002 FLORIDA |
| ADMINISTRATIVE CODE. |
| NOTE: ONE OF OF TRUSS PACKAGE WILL BE HELD IN THIS |
| OFFICE TO BE SUBMITTED TO THE BOARD OF ENGINEERS FOR |
| THEIR REVIEW. |
| |
| B) TRUSS LOADING DOESN'T MATCH DESIGNCRITERIA |
| SPECIFIED BY THE ENGINEER OF RECORD. REVISE AS |
| REQUIRED. |
| |
| C) THERE IS AN ENGINEER OF RECORD IN THIS PROJECT. |
| HIS NAME MUST BE INCLUDED IN THE TRUSS PACKAGE AS |
| REQUIRED BY SEC. 61G15-31.003 FLORIDA ADMINISTRATIVE |
| CODE. |
| |
| D) ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE |
| TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. |
| |
| E) CLARIFY WHY THE ATTIC LIVE LOAD IS NONCONCURRENT. |
| TABLE R301.5OF 2004 FLORIDA RESIDENTIAL CODE REQUIRES |
| THIS LOAD TO BE CALCULATED ON THE TRUSSES.CLEARLY |
| SPECIFY WHAT SECTION OF THE CODE ALLOWS THIS LOAD TO BE |
| NONCONCURRENT AND IS NONCONCURRENT WITH WHAT OTHER |
| LOADS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |