Plan Review Notes
Plan Review Notes For Permit 07060292
Permit Number 07060292
Review Stop B
Sequence Number 3
Notes
Date Text
2007-10-26 17:00:16NEW SINGLE FAMILY RESIDENCE BUILDING REVIEW THIRD
 CHECKLIST.
 REVIEW UNDER FLORIDA RESIDENTIAL CODE 2004 AND FBC 2004
 WITH 2006 REVISIONS.
  
 1- NEED TO GET APPROVAL FROM ZONING. SEE ZONING
 COMMENTS.
  
 2- SHEET 3.1 SPECIFIES CONSTRUCTION TYPE III.SPECIFY
 WHAT TYPE III.A OR B?.ALSO,BE AWARE THAT TYPE III
 CONSTRUCTION REQUIRES A TWO HOUR FIRE RATED WALL. SEE
 TABLE 601 AND TABLE 602 OF FBC 2004. NEED TO SPECIFY
 HOW ACHIEVING THE 2 HOUR FIRE RATING REQUIRED BY TABLES
 601 AND 602 FBC 2004.
  
 3- PROVIDE COMPLETE MANUFACTURER SPECS FOR 2 HOUR
 CONCRETE BLOCK AS REQUIRED BY ITEM 2 ABOVE.
  
 4- RE-SUBMITTAL FEEOF $193.10 WAS NOT PAID AT TIME OF
 SUBMITTAL.IN ADDITION, NEW RE-SUBMITTAL FEEWILL BE
 DUE AT TIME OF RE-SUBMITTAL.
  
 5- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE.(REPEAT COMMENT).
  
 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 ***NOTE: REMEMBER THAT ENGINEER OF RECORD NEEDS TO
 REVIEW AND APPROVE ALL PRODUCT APPROVALS IN WRITING
 (NOT SIGNING AND SEALING) PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 A) PRECAST LINTELS. PROVIDE CURRENT FLORIDA PRODUCT
 APPROVAL REPORT FL158-R2. THIS IS THE ONE THAT
 REFERENCES NOA 06-0222.01 SUBMITTED.ONE SUBMITTED IS
 FL158-R1 WHICH IS THE OLD ONE AND WAS REVISED.
  
 B) SINGLE HUNG WINDOWS. PROVIDE CURRENT FLORIDA
 PRODUCT APPROVAL REPORT FL239-R10 AND CORRESPONDING
 NOA.FL239-R4 IS OLD AND WAS REVISED.
  
 7- STORM SHUTTERS:
 A) INSTALLATION SCHEDULE SUBMITTED SHOWS 12.5"
 ANCHOR SPACING. LOOK AT STORM PANEL DETAIL #1 ON SHEET
 1 OF 6 OF STORM SHUTTERS DRAWINGS AND REVISE AS
 REQUIRED.
  
 B) REVISE MINIMUM PANEL LENGTH FOR THE FOLLOWING
 OPENINGS: #1, #3, #5 AND #8.SEE TABLE 2 ON PAGE 6 OF
 6 OF SHUTTERS DRAWINGS SUBMITTED.
  
 C) CLEARLY SPECIFYSHUTTER MOUNTING CONDITION ON
 THE 4TH COLUMN OF STORM SHUTTER INSTALLATIONSCHEDULE.
 EG:NEED TO SPECIFYIFWALL MOUNTED OR BUILT OUT,
 ETC.TO VERIFY COMPLIANCE WITH WIND LOADS SEC. 1609
 FBC 2004.(REPEAT COMMENT).
  
 D) PROVIDE KEY PLAN TO IDENTIFY OPENING LOCATION TO
 VERIFY COMPLIANCE WITH WIND LOADS SEC. 1609 FBC 2004.
 (REPEAT COMMENT).
  
 8- ROOF DESIGN LOADS ON SHEET 5.1 IS MISSING THE ATTIC
 LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 9- A) SURVEY SUBMITTED NEEDS THE SURVEYOR ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 B) SURVEY TO HAVE COMPLETE ADDRESS NUMBER.
  
 10- TRUSS PACKAGE:
 A) ENGINEER TO PROVIDE ORIGINAL SIGNATURE, NOT
 RUBBER STAMP SIGNATURE.SEC. 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
 NOTE: ONE OF OF TRUSS PACKAGE WILL BE HELD IN THIS
 OFFICE TO BE SUBMITTED TO THE BOARD OF ENGINEERS FOR
 THEIR REVIEW.
  
 B) TRUSS LOADING DOESN'T MATCH DESIGNCRITERIA
 SPECIFIED BY THE ENGINEER OF RECORD. REVISE AS
 REQUIRED.
  
 C) THERE IS AN ENGINEER OF RECORD IN THIS PROJECT.
 HIS NAME MUST BE INCLUDED IN THE TRUSS PACKAGE AS
 REQUIRED BY SEC. 61G15-31.003 FLORIDA ADMINISTRATIVE
 CODE.
  
 D) ENGINEER OF RECORD NEEDS TO REVIEW AND APPROVE
 TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 E) CLARIFY WHY THE ATTIC LIVE LOAD IS NONCONCURRENT.
 TABLE R301.5OF 2004 FLORIDA RESIDENTIAL CODE REQUIRES
 THIS LOAD TO BE CALCULATED ON THE TRUSSES.CLEARLY
 SPECIFY WHAT SECTION OF THE CODE ALLOWS THIS LOAD TO BE
 NONCONCURRENT AND IS NONCONCURRENT WITH WHAT OTHER
 LOADS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712