2007-08-20 16:21:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 11A STATES AIR HANDLER
 INTERIOR, MECHANICAL PLANS SHOW THE AIR HANDLER IS IN
 THE GARAGE, PLEASE CORRECT ENERGY CALCULATIONS.
  
 2) MECHANICAL PLANS NOTES STATE "ACCORDING TO
 F.M.C.2004. AS THIS IS A SINGLE FAMILY DWELLING IT
 NEEDS TO COMPLY WITH THE 2004 FBC/RESIDENTIAL, SEE
 R101.2. PLEASE CORRECT.
  
 3) MECHANICAL PLANS EQUIPMENT SCHEDULE, CAN NOT READ
 THE CONDENSER UNIT MODEL NUMBER, SEE 2004 FBC 106.1.1.
 PLEASE CORRECT.
  
 4) PLEASE SHOW THE A/C SYSTEM'S SEER IN THE EQUIPMENT
 SCHEDULE.
  