2007-08-17 16:59:11NEW SINGLE FAMILY RESIDENCE BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004 WITH 2006 REVISIONS.
  
 1- TYPE OF CONSTRUCTION SPECIFIED ON SHEET 3.1 IS
 WRONG. SEE SEC. 602.1 FBC 2004 AND REVISE AS REQUIRED.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115) TO PAY IMPACT FEES.BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT.REPEATED COMMENT FROM
 PREVIOUS CHECKLIST.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. REPEATED COMMENT FROM
 PREVIOUS CHECKLIST.
  
 4- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. SEC.
 R401.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: WATER CAN'T BE DIRECTED TO NEIGHBOR'S
 PROPERTY. REPEATED COMMENT FROM PREVIOUS CHECKLIST.
  
 5- SHEET 1.1:
 A) REVISE PLYWOOD ROOF SHEATHING NOTE D.MINIMUM
 FASTENER PENETRATIONIS 1 3/4" AS REQUIRED BY ASTM
 C-926 AND ASTM C-1063.THEREFORE 1 3/4" NAILING AS
 SPECIFIED ON THIS NOTE IS NOT ADEQUATE. SEE ASTM
 STANDARDS AND REVISE AS REQUIRED.
  
 B) UPDATE ALL GENERAL NOTES. SEE CHAPTER 43 OF 2004
 FLORIDA RESIDENTIAL CODE FOR SPECIFIC STANDARDS AND
 SPECIFIC YEAR TO BE USED. REPEATED COMMENT FROM
 PREVIOUS CHECKLIST.
  
 6- OWES $415.47 FOR UPDATED VALUATION AND RADON FEES.
 REPEATED COMMENT FROM PREVIOUS CHECKLIST.
  
 7- PROVIDE SOIL TEST REPORT. REPEATED COMMENT-FROM
 PREVIOUS CHECKLIST.
  
 8- ENERGY CALCULATIONS NEED TO HAVE CORRECT BUILDER'S
 NAME. REPEATED COMMENT FROM PREVIOUS CHECKLIST.
  
 9- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) PRECAST LINTELS.NOA 03-0605.05 SUBMITTED
 EXPIRED ON 05/21/06. ON THE OTHER HAND NOA 03-0605.04
 IS FOR 4", 6" AND 12" WIDE LINTELS. THEREFORE IT CAN BE
 USED IN THIS PROJECT BECAUSE THIS LINTEL SIZE IS NOT
 SPECIFIED ON PLANS.
  
 B) SINGLE HUNG WINDOWS. NOA 05-0928.03 SUBMITTED
 DON'T CORRESPOND TO FL239-R4 SUBMITTED. GO THE THE DCA
 WEBSITE WWW.FLORIDABUILDING.ORG TO DOWNLOAD NOA THAT
 CORRESPONDS TO FL239.
  
 C) ENTRY DOOR AS SHOWN ON PLANS. REPEAT COMMENT FROM
 PREVIOUS CHECKLIST.
  
 D) FRENCH DOORS AS SHOWN ON PLANS.NOA 05-0107.01
 SUBMITTED DOESN'T CORRESPOND TO FL253-R2 SUBMITTED. GO
 TO DCA WEBSITE TO DOWNLOAD CORRESPONDING NOA.
 ***NOTE: THERE ARE TWO DIFFERENT PRODUCT APPROVALS
 SUBMITTED. PROVIDE ONLY ONE PRODUCT APPROVAL. ON THE
 OTHER HAND NOA 02-1216.09 EXPIRED ON 08/15/07.
 THEREFORE IT CAN'T BE USED.
  
 10- STORM SHUTTERS:
 A) COMPLETE ALL THE INFORMATION IN THE INSTALLATION
 SCHEDULE SUBMITTED. NEED TO SPECIFY SHUTTER MOUNTING
 CONDITION (EG: WALL MOUNTED, BUILT OUT MOUNTED, ETC.),
 SHUTTER SPAN, SPECIFIC ANCHOR AND SUBSTRATE (STRUCTURE
 TO BE ATTACHED TO: CONCRETE BLOCK).
  
 B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC ANCHOR
 TYPE. SEE SHEET 5 OF 6 OFSHUTTERS DRAWINGS.
  
 C) PROVIDE KEY PLAN TO IDENTIFY LOCATION OF
 OPENINGS.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 12- SHEET 2.1: REVISE WINDOW BUCK DETAIL. SEE SEC.
 R613.6.2 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT
 WAY OF SHOWING BUCK DETAIL.BUCK NEEDS TO PROVIDE
 FULL FRAME SUPPORT. REPEAT COMMENT FROM PREVIOUS
 CHECKLIST.
  
 13- SHEET 5.1:ROOF DESIGN LOADS INFORMATION DOESN'T
 MATCH INFORMATION SHOWN ON SHEET. 1.1.REVISE AS
 REQUIRED. REPEATED COMMENT FROM PREVIOUS CHECKLIST.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER