2007-10-11 08:23:34 
  
 BUILDING PLAN REVIEW
 PERMIT: 07060275
 ADD: 4325 N. HAVERHILL RD
 CONT: JOE SCHMIDT CONST. INC.
 TEL: (561)748-7811
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
 10/11/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)SINKS REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1
 SHALL COMPLY WITH SECTION 11-4.24. SHOW COMPLIANCE.
 **NOTED**
 HOWEVER, SHEET 3 ELEVATION #3 SHALL INDICATE THE
 REQUIRED DIMENSIONS FOR THE HEIGHT OF THE COUNTER, KNEE
 CLEARANCE, DEPTH OF THE SINK, CLEAR FLOOR SPACE ETC.
 THE COUNTER SHALL NOT BE HIGHER THAN 34 INCHES ABOVE
 THE FINISH FLOOR. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND SHOW SUFFICIENT CLARITY TO INDICATE THE
 NATURE AND EXTENT OF THE WORK PROPOSED. 106.1.1
  
 3)61G15-23.002.ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER SHALL BE
 ON EACH PAGE.
 **NOTED**
 WPB AMENDMENTS.106.1.3 THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTIONS PROGRAM. THE ?HAND
 WRITTEN? INFORMATION ON THE DRAWINGS IS NOT ACCEPTABLE.
 SUBMIT TWO NEW SETS OF DRAWINGS WITH ALL REQUIRED
 INFORMATION.
  
 NOTE:IF THIS IS A TYPE I OR II BUILDING, THE BACKING
 FOR THE CABINETS SHALL BE FIRE RETARDANT-TREATED WOOD.
 **OK**
  
 **NEW**
 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected].