Plan Review Notes
Plan Review Notes For Permit 07060266
Permit Number 07060266
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-28 17:17:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE ANCHOR CHARTS ARE FOR 3 1/2" EDGE DISTANCE.
 YOU HAVE SPECIFIED 2", SO A FACTOR OF .50 MUST BE
 APPLIED (SEE SHEET 6).
  
 2.)YOU'VE CIRCLED AND SPECIFIED ANCHORING FOR
 CONCRETE, BUT HAVE STATED THAT THIS IS CONCRETE BLOCK.
 MASONRY SUBSTRATE NOT ALLOWED FOR CONNECTIONS 2, 9
 (TOP), SEE SHEET7 OF THE PRODUCT APPROVAL.
  
 3.)SEE OPENING 7, WHICH HAS A DESIGN PRESSURE OF
 -40.02.YOU CANNOT USE THE -40 CHART, MUST USE THE
 CHART >-40 TO -60.
  
 4.)CHECK AND REVISE ALL OPENINGS.