Plan Review Notes For Permit 07060266 |
Permit Number |
07060266 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-06-28 17:17:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.)THE ANCHOR CHARTS ARE FOR 3 1/2" EDGE DISTANCE. | | YOU HAVE SPECIFIED 2", SO A FACTOR OF .50 MUST BE | | APPLIED (SEE SHEET 6). | | | | 2.)YOU'VE CIRCLED AND SPECIFIED ANCHORING FOR | | CONCRETE, BUT HAVE STATED THAT THIS IS CONCRETE BLOCK. | | MASONRY SUBSTRATE NOT ALLOWED FOR CONNECTIONS 2, 9 | | (TOP), SEE SHEET7 OF THE PRODUCT APPROVAL. | | | | 3.)SEE OPENING 7, WHICH HAS A DESIGN PRESSURE OF | | -40.02.YOU CANNOT USE THE -40 CHART, MUST USE THE | | CHART >-40 TO -60. | | | | 4.)CHECK AND REVISE ALL OPENINGS. |
|