Plan Review Notes
Plan Review Notes For Permit 07060235
Permit Number 07060235
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-07-06 14:08:45***DENIED***
  
 PLEASE NOTE THAT THERE IS NO RESPONSE TO THE FIRST FIRE
 REVIEW. PLEASE SEE REVIEW COMMENTS TAKEN FROM PREVIOUS
 FIRE REVIEW:
  
 1) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2) THE REMOVAL OF AND/OR THE STOCKING OF NEW BUILDING
 MATERIALS AND SUPPLIES SHALL NOT HINDER, INTERFERE OR
 OBSTRUCT ACCESS TO OR EGRESS FROM THE PROPERTY
 INCLUDING THE FLOOR'S EXIT CORRIDORS.
  
 3) PLEASE INDICATE IF THE ERECTION OF THE NEW PARTITION
 WALL IMPACTS FIRE SPRINKLER DEVICES. SEPARATE SHOP
 DRAWINGS AND PERMIT IS REQUIRED IF THE FIRE PROTECTION
 SYSTEM HAS TO BE MODIFIED.
 PLEASE RESPOND ON PLANS OR RESPONSE LETTER
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756