Plan Review Notes
Plan Review Notes For Permit 07060197
Permit Number 07060197
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-07-24 19:03:26*****UNSAT******
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 07.INDICATE THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS AS CLASS A, CLASS B, OR CLASS C.BE SPECIFIC
 IN TERMS OF CLASS A, CLASS B, OR CLASS C IN THE EXITS,
 EXIT ACCESS CORRIDORS, AND OTHER AREAS.
  
 08.INDICATE THE LOCATION OF THE EMERGENCY LIGHTS.
 EMERGENCY LIGHT(S) APPEAR TO BE LACKING IN THE SOUTH
 END OF CORRIDOR 001;SEE SHEETSA-2,E1.1
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLAN) EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW