Plan Review Notes For Permit 07060197 |
Permit Number |
07060197 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-07-24 19:03:26 | *****UNSAT****** | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 07.INDICATE THE NEW INTERIOR WALL AND CEILING FINISH | | MATERIALS AS CLASS A, CLASS B, OR CLASS C.BE SPECIFIC | | IN TERMS OF CLASS A, CLASS B, OR CLASS C IN THE EXITS, | | EXIT ACCESS CORRIDORS, AND OTHER AREAS. | | | | 08.INDICATE THE LOCATION OF THE EMERGENCY LIGHTS. | | EMERGENCY LIGHT(S) APPEAR TO BE LACKING IN THE SOUTH | | END OF CORRIDOR 001;SEE SHEETSA-2,E1.1 | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE (ON THE PLAN) EACH COMMENT WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|