Plan Review Notes
Plan Review Notes For Permit 07060197
Permit Number 07060197
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-12 15:23:39 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, WITH
 ORIGINAL COMMENT NUMBER ATTACHED.
  
 2} NOTE: PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS
 SHALL BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR
 FOR THE CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE
 SEE ARTICLE.
 A)COMMENT TO RESPONSE. THIS ARTICLE DOES APPLY.AS
 THERE ARE NO EXEPTIONS LISTED IN THAT ARTICLE. SEE
 DETAIL #1, SHEET E7.1, DETAILS 02, 03, 04 AND 05, SHEET
 A-2.. A NOTE ON THE PLAN REFERENCING THIS ARTICLE WILL
 SUFFICE
  
 5} PROVIDE EMERGENCY ILLUMINATION PER
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC. INDICATE SAME ON PLANS.
 A) THIS IS REQUIRED IN THE PLAN REVIEW STAGE OF THE
 PERMITTING PROCESS, THE CIRCUITING MUST BE REVIEWED FOR
 COMPLIANCE.
  
 6} INDICATE CIRCUIT NUMBERS ON ALL ADDED DEVICES AND
 ALL DEVICES ON THAT CIRCUIT, SO THAT 220.14(I) MAY BE
 REVIEWED. NOTE #2 ON THE ELECTRICAL SHEETS REQUIRES A
 CALCULATION BEFORE ASSEMING MORE DEVICES MAY BE ADDED.
 A) SAME COMMENT AS ABOVE..
  
 7} SAME AS COMMENT #6 BUT FOR ADDED FIXTURE LOADS.
 INDICATE CIRCUIT NUMBERS.
  
 SEE 553.80(2)(B), ATTACHED, REGARDING DESIGN
 PROFESSIONALS DOCUMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718