2007-07-12 15:23:39 | |
| |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, WITH |
| ORIGINAL COMMENT NUMBER ATTACHED. |
| |
| 2} NOTE: PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS |
| SHALL BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR |
| FOR THE CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE |
| SEE ARTICLE. |
| A)COMMENT TO RESPONSE. THIS ARTICLE DOES APPLY.AS |
| THERE ARE NO EXEPTIONS LISTED IN THAT ARTICLE. SEE |
| DETAIL #1, SHEET E7.1, DETAILS 02, 03, 04 AND 05, SHEET |
| A-2.. A NOTE ON THE PLAN REFERENCING THIS ARTICLE WILL |
| SUFFICE |
| |
| 5} PROVIDE EMERGENCY ILLUMINATION PER |
| NFPA-101 7.8 (2003), AND CIRCUITED PER |
| 700.12 NEC. INDICATE SAME ON PLANS. |
| A) THIS IS REQUIRED IN THE PLAN REVIEW STAGE OF THE |
| PERMITTING PROCESS, THE CIRCUITING MUST BE REVIEWED FOR |
| COMPLIANCE. |
| |
| 6} INDICATE CIRCUIT NUMBERS ON ALL ADDED DEVICES AND |
| ALL DEVICES ON THAT CIRCUIT, SO THAT 220.14(I) MAY BE |
| REVIEWED. NOTE #2 ON THE ELECTRICAL SHEETS REQUIRES A |
| CALCULATION BEFORE ASSEMING MORE DEVICES MAY BE ADDED. |
| A) SAME COMMENT AS ABOVE.. |
| |
| 7} SAME AS COMMENT #6 BUT FOR ADDED FIXTURE LOADS. |
| INDICATE CIRCUIT NUMBERS. |
| |
| SEE 553.80(2)(B), ATTACHED, REGARDING DESIGN |
| PROFESSIONALS DOCUMENTS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |