2007-06-22 12:28:18 | *****DENIED***** |
| |
| |
| 01.ON SHEET A-T1 UNDER APPLICABLE CODES, AMEND TO |
| REFLECT THAT NFPA 1 (2003 EDITION) AND NFPA 101 (2003 |
| EDITION) SHALL BE REFERENCED. |
| |
| 02.PLEASE EXPLAIN THE REFERENCES TO NFPA 45, NFPA |
| 88B-97, AND NFPA 102-95 UNDER THE APPLICABLE CODES. ARE |
| THESE REFERENCES PERTINENT TO THE PROPOSED SCOPE OF |
| WORK? |
| |
| 03.THE TENANT SPACE SUITE NUMBER SHALL BE IN THE |
| TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| |
| 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE PREMISES AT THE END OF EACH |
| SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE |
| OPERATION. |
| |
| 06.THE REMOVAL OF EXISTING AND/OR THE STOCKING OF NEW |
| BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE OR |
| HINDER ACCESS TO OR EGRESS FROM THE SAID TENANT SPACE |
| OR OTHER TENANT SPACES ON THE 17TH FLOOR. |
| |
| 07.INDICATE THE NEW INTERIOR WALL AND CEILING FINISH |
| MATERIALS AS CLASS A, CLASS B, OR CLASS C.BE |
| SPECIFIC |
| |
| 08.INDICATE THE LOCATION OF THE EMERGENCY LIGHTS. |
| |
| 09.PLANS DO NOT STATE OR SHOW THE PRESENCE OF THE |
| TENANT SPACE BEING SPRINKLERED.IF SPRINKLERED AND |
| MODICATIONS TO THE SYSTEM IS NEEDED, SEPARATE PLANS AND |
| PERMIT SHALL BE REQUIRED. |
| |
| 10.PLANS DO NOTSTATE OR SHOW THE PRESENCE OF FIRE |
| ALARM OR FIRE ALARM DEVICES FOR THIS TENANT SPACE.IF |
| SO EQUIPPED AND MODICATIONS TO THE SYSTEM IS NEEDED, |
| SEPARATE PLANS AND PERMIT WILL BE REQUIRED. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE (ON THE PLAN) EACH COMMENT WAS |
| ADDRESSED |
| |
| |