Plan Review Notes
Plan Review Notes For Permit 07060197
Permit Number 07060197
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-22 12:28:18*****DENIED*****
  
  
 01.ON SHEET A-T1 UNDER APPLICABLE CODES, AMEND TO
 REFLECT THAT NFPA 1 (2003 EDITION) AND NFPA 101 (2003
 EDITION) SHALL BE REFERENCED.
  
 02.PLEASE EXPLAIN THE REFERENCES TO NFPA 45, NFPA
 88B-97, AND NFPA 102-95 UNDER THE APPLICABLE CODES. ARE
 THESE REFERENCES PERTINENT TO THE PROPOSED SCOPE OF
 WORK?
  
 03.THE TENANT SPACE SUITE NUMBER SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE PREMISES AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE
 OPERATION.
  
 06.THE REMOVAL OF EXISTING AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE OR
 HINDER ACCESS TO OR EGRESS FROM THE SAID TENANT SPACE
 OR OTHER TENANT SPACES ON THE 17TH FLOOR.
  
 07.INDICATE THE NEW INTERIOR WALL AND CEILING FINISH
 MATERIALS AS CLASS A, CLASS B, OR CLASS C.BE
 SPECIFIC
  
 08.INDICATE THE LOCATION OF THE EMERGENCY LIGHTS.
  
 09.PLANS DO NOT STATE OR SHOW THE PRESENCE OF THE
 TENANT SPACE BEING SPRINKLERED.IF SPRINKLERED AND
 MODICATIONS TO THE SYSTEM IS NEEDED, SEPARATE PLANS AND
 PERMIT SHALL BE REQUIRED.
  
 10.PLANS DO NOTSTATE OR SHOW THE PRESENCE OF FIRE
 ALARM OR FIRE ALARM DEVICES FOR THIS TENANT SPACE.IF
 SO EQUIPPED AND MODICATIONS TO THE SYSTEM IS NEEDED,
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLAN) EACH COMMENT WAS
 ADDRESSED
  
  