2007-06-20 08:02:50 | |
| |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| CHANGE. |
| |
| 2} NOTE: PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS |
| SHALL BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR |
| FOR THE CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE |
| SEE ARTICLE. |
| |
| 3} THE "SIMPLEX LOCK" NOTED ON SHEET A-E1, MUST BE |
| PERMITEDUNDER SEPARATE APPLICATION, WITH ALL |
| EQUIPMENT SPECIFICATION. |
| |
| 4} SHEET NOTES ON ELECTRICAL SHEETS INDICATE A SHEET |
| E7.2, THIS SHEET IS MISSING. |
| |
| 5} PROVIDE EMERGENCY ILLUMINATION PER |
| NFPA-101 7.8 (2003), AND CIRCUITED PER |
| 700.12 NEC. INDICATE SAME ON PLANS. |
| |
| 6} INDICATE CIRCUIT NUMBERS ON ALL ADDED DEVICES AND |
| ALL DEVICES ON THAT CIRCUIT, SO THAT 220.14(I) MAY BE |
| REVIEWED. NOTE #2 ON THE ELECTRICAL SHEETS REQUIRES A |
| CALCULATION BEFORE ASSEMING MORE DEVICES MAY BE ADDED. |
| |
| 7} SAME AS COMMENT #6 BUT FOR ADDED FIXTURE LOADS. |
| INDICATE CIRCUIT NUMBERS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |