Plan Review Notes
Plan Review Notes For Permit 07060182
Permit Number 07060182
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-11 10:37:02CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON,CBO PERMIT NO 07060182
 BUILDING PLAN EXAMINERII PROJECT COOLING TOWER
 REPLACEMENT
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 515 N. FLAGLER
 DRIVE
  CONTRACTOR AIRSTRON, INC.
  DATE SEPTEMBER 11, 2007
 STRUCTURALPLANREVIEW (2) F.S.
 713.13 NOTICE OF COMMENCEMENT TO BE FILED WITH THE
 CLERK OF COURT
 F.S.713.13 (2) IF THE WORK DESCRIBED
 IN THE NOTICE OF COMMENCEMENT IS NOT COMMENCED WITHIN
 90 DAYS AFTER RECORDING THEREOF, SUCH NOTICE IS NULL
 AND VOID
 RESUBMIT A NEWLY RECORDED NOTICE OF COMMENCEMENT PRIOR
 TO PERMIT ISSUANCE.
  
 (4) SHEETS-1 PROVIDE WIND IMPORTANCE FACTOR ON DATA
  
  
 (5) SHEET S-2 SUBMIT DETAIL OFCOOLING TOWER WITH ALL
 SUPPORTS. IDENTIFY HIGHEST POINT OF
  
 TOWER FROM ROOF SLAB
  
 (6) SHEET S-1 INFORMATION ON ARBAB ENGINEERING, INC.
 SHEET 10 OF 25 DOES NOT MATCH
  
 SHEET S-1DRAWINGS
  
 (7) SHEET S-2 FBC 1905.1.1STRENGTH OF CONCRETE
  STATE DESIGN STRENGTH FOR FORMED CONCRETE COLUMN
  
 (8) SHEET S-1 PROVIDE INFORMATION STATING?
 MODIFICATION ? OF STUB COLUMN
  
 (9) SHEET S-2 SEE PROTECTION OF METALS AS
 SPECIFIED ON SHEET M-2 ?TYPICAL ROOF MOUNTED
  
 PIPING SERVICE SUPPORT INSTALLATION?PROVIDE
 PROTECTION FOR STRUCTURAL SUPPORTS
  
 COMPATIBLE WITH THAT SPECIFIED ON SHEET M-2.