2007-07-02 17:38:52---------------DENIED-------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 NFPA 214-96
  
 1. SCHEMATIC AND INLET DETAILS SECTION IS NOT LEGIBLE.
 PLEASE PROVIDE MARLEY SCHEMATIC THAT IS OF LEGIBLE
 SIZE, QUALITY AND CLARITY. FBC 106.1.3
  
 2. DETAILS FOR PIPE STANDS AND CLAMPS: SUFFICIENT
 INFORMATION IS NOT PROVIDED WITH DETAILS AS SHOWN ON
 PLAN. PROVIDE ALL RELEVANT INFORMATION ON PLANS, SUCH
 AS SIZE, FASTENERS TO BE USED, SPACING OF SUPPORTS,
 ETC. RATHER THAN REFERRING TO A CATALOG WHICH WAS NOT
 PROVIDED WITH THE APPLICATION. FBC 106.1.1, 106.1.3
  
 3. PROVIDE MANUFACTURER'S SUBMITTAL DATA AND
 INSTALLATION INSTRUCTIONS FOR THE COOOLING TOWER. FBC,M
 908.1
  
 4. PROVIDE WIND LOAD CALCULATIONS FOR THE COOLING
 TOWER, SUPPORTS AND ANCHORING SHOWING THE DESIGN TO BE
 ADEQUATE FOR THE WIND ZONE AND EXPOSURE CATEGORY OF THE
 JOB LOCATION PER FBC,M 301.13 AND FBC CH.16.
  
 5. PLEASE REFERENCE CODES IN EFFECT AT TIME OF PERMIT
 APPLICATION: FBC 2004 W/2006 REVISIONS, NFPA 214-96.
  
 NOTE: ADDITIONAL COMMENTS ARE POSSIBLE PENDING THE
 INCLUSION OF INFORMATION WHICH IS MISSING AT THIS
 TIME.
  