2007-06-21 20:01:16 | *** UNSAT *** |
| |
| 1) NOTE:PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE |
| THE CODES TO BE STATED ON PLANS. |
| PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| PLEASE LIST THE FOLLOWING |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| |
| 2) NOTE: PLEASE PROVIDE INFORMATION FOR ANY INCREASE OF |
| LOADS FROM EXISTING EQUIPMENT TO NEW EQUIPMENT. THIS |
| INFORMATION SHOULD BE STATED ON PLANS. |
| 220. |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE RISER MENTIONS FOR GUTTER TO BE |
| REPLACE PER NEC HOWEVER NO SIZE OR DIMENSIONS ARE SHOWN |
| AS NEEDED PER NEC 366. |
| FBC 106.1.2 |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |