2007-08-08 16:10:32****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 FOURTH REVIEW BUT FIRST REVIEW FOR INSTALLATION
 SCHEDULE
  
 1.)SHUTTER MOUNTING CONNECTION TYPE (INSTALLATION
 SCHEDULE) SHOULD BE THE CONNECTION TYPE, C1 THROUGH C5,
 SEE SHEET 5 OF THE PRODUCT APPROVAL.
  
 2.)INSTALLATION SCHEDULE STATES THAT YOU WILL BE
 INSTALLING TAPCONS.THERE ARE TWO TYPES, ELCO AND ITW,
 AND YOU HAVE HIGHLIGHTED ELCO BUT HIGHLIGHTED ANCHORING
 FOR ITW, WHICH REQUIRES 6" ANCHOR SPACING, BUT YOU
 SPECIFY 12".COMPLETE INFORMATION REQUIRED ON THE
 INSTALL SCHEDULE (SEE NOTE ON THE BOTTOM OF THE
 INSTALLATION SCHEDULE WHICH STATES "ANCHOR TYPE MUST BE
 SPECIFIC, EG THERE ARE DIFFERENT TYPES OF TAPCONS WITH
 DIFFERENT STRENGTH VALUES"THERE IS INCOMPLETE
 INFORMATION ON THE SCHEDULE AND INCONSISTENT
 INFORMATION ON THE PRODUCT APPROVAL.