2008-08-12 12:53:53 | |
| ** DENIED PLANS.** |
| |
| ** NEW PLANS ONCE AGAIN WHICH ARE COMPLETELY REVISED |
| FROM PREVIOUS PLANS. |
| ** NEW DESIGNER OF RECORD. |
| |
| 1) NOTE: THE GENERATOR IS NOW BEING SHOWN AS A |
| SEPARATELY DERIVED SYSTEM HOWEVER THE RISER INDICATES A |
| 3-POLE TRANSFER SWITCH. |
| PLEASE EXPLAIN HOW THIS IS POSSIBLE. |
| 250.20, 250.30, ETC. |
| |
| 2) NOTE: AN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| 250.110,250.24,250.122 ETC. |
| THE RISER FOR FEEDERS FROM ATS TO EXISTING MAIN AT |
| BUILDING IS MISSING AN EQUIPMENT GROUNDING CONDUCTOR. |
| 250.32, 250.122. |
| MUST ALSO PLACE NOTE ON PLANS TO SEPARATE ALL NEUTRALS |
| AND EQUIPMENT GROUNDING AT EXISTING MAIN ONE OF ONE. |
| |
| |
| ** MUST INSTALL EQUIPMENT GROUNDING. THE ONLY WAY |
| EQUIPMENT GROUNDING IS NOT REQUIRED IS *IF* THERE ARE |
| NO OTHER METAL CURRENT CARRYING PARTS BETWEEN SOURCES |
| OR EQUIPMENT. BASED ON THE BRANCH CIRCUIT FROM THE |
| EXISTING SERVICE TO GENERATOR AND OTHER POSSIBLE |
| CURRENT CARRYING PARTS THIS IS REQUIRED. |
| |
| 3) NOTE: BASED ON COMMENT #1 ABOVE PLEASE SUBMIT |
| REVISED SPECS/CUT SHEETS FOR TRANSFER SWITCH. 110.3, |
| 90.7 |
| |
| 4) NOTE: THIS RISER IS NOW SHOWING MAINS AND |
| DISCONNECTING MEANS WHICH WERE NEVER PREVIOUSLY SHOWN. |
| ALL MAINS AND MEANS OF DISCONNECT SHALL MEET CODE FOR |
| GROUPING AND ALSO FOR SIGNAGE REQUIRED AND LABELING ALL |
| MEANS OF DISCONNECT FOR SHUTTING DOWN POWER UNDER BOTH |
| CONDITIONS. |
| 230.2E, 700.8, 701.9, 702.8 |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |