Plan Review Notes
Plan Review Notes For Permit 07060173
Permit Number 07060173
Review Stop E
Sequence Number 4
Notes
Date Text
2008-08-12 12:53:53 
 ** DENIED PLANS.**
  
 ** NEW PLANS ONCE AGAIN WHICH ARE COMPLETELY REVISED
 FROM PREVIOUS PLANS.
 ** NEW DESIGNER OF RECORD.
  
 1) NOTE: THE GENERATOR IS NOW BEING SHOWN AS A
 SEPARATELY DERIVED SYSTEM HOWEVER THE RISER INDICATES A
 3-POLE TRANSFER SWITCH.
 PLEASE EXPLAIN HOW THIS IS POSSIBLE.
 250.20, 250.30, ETC.
  
 2) NOTE: AN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED
 AFTER THE FIRST MEANS OF DISCONNECT.
 250.110,250.24,250.122 ETC.
 THE RISER FOR FEEDERS FROM ATS TO EXISTING MAIN AT
 BUILDING IS MISSING AN EQUIPMENT GROUNDING CONDUCTOR.
 250.32, 250.122.
 MUST ALSO PLACE NOTE ON PLANS TO SEPARATE ALL NEUTRALS
 AND EQUIPMENT GROUNDING AT EXISTING MAIN ONE OF ONE.
  
  
 ** MUST INSTALL EQUIPMENT GROUNDING. THE ONLY WAY
 EQUIPMENT GROUNDING IS NOT REQUIRED IS *IF* THERE ARE
 NO OTHER METAL CURRENT CARRYING PARTS BETWEEN SOURCES
 OR EQUIPMENT. BASED ON THE BRANCH CIRCUIT FROM THE
 EXISTING SERVICE TO GENERATOR AND OTHER POSSIBLE
 CURRENT CARRYING PARTS THIS IS REQUIRED.
  
 3) NOTE: BASED ON COMMENT #1 ABOVE PLEASE SUBMIT
 REVISED SPECS/CUT SHEETS FOR TRANSFER SWITCH. 110.3,
 90.7
  
 4) NOTE: THIS RISER IS NOW SHOWING MAINS AND
 DISCONNECTING MEANS WHICH WERE NEVER PREVIOUSLY SHOWN.
 ALL MAINS AND MEANS OF DISCONNECT SHALL MEET CODE FOR
 GROUPING AND ALSO FOR SIGNAGE REQUIRED AND LABELING ALL
 MEANS OF DISCONNECT FOR SHUTTING DOWN POWER UNDER BOTH
 CONDITIONS.
 230.2E, 700.8, 701.9, 702.8
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]