2008-05-30 08:09:57 | ** DENIED 3RD REVIEW ** |
| |
| ** PLEASE SEE SEVERAL NEW COMMENTS ARE NOW BASED ON |
| COMPLETELY REVISED ELECTRICAL RISER DIAGRAM WHICH NOW |
| CONTAINS SEVERAL NEW CHANGES WHICH WERE NOT PART OF |
| PREVIOUSLY SUBMITTED PLANS. |
| |
| 1) NOTE: PLEASE SEE PLANS NOW SHOW A NEW 500KVA |
| TRANSFORMER WHICH WAS NOT PART OF PREVIOUS PLANS. |
| PLEASE SEE 250.20,250.30 AS THIS IS NOW A SEPARATELY |
| DERIVED SYSTEM. |
| |
| 2) NOTE: PLEASE SEE THE TRANSFORMER AS NOTED ABOVE IS |
| ALSO SHOWING NEUTRAL CONDUCTORS TO THE TRANSFORMER. HOW |
| IS THIS POSSIBLE WHEN THE TRANSFORMER IS SEPARATELY |
| DERIVED? |
| PLEASE COMPLETE PLANS, CONDUCTORS, RISER, GROUNDING |
| ELECTRODE SYSTEM ETC PER 2005 NEC. |
| THERE ARE TOO MANY CODE SECTIONS TO NOTE. |
| FBC 106.3.5.1.2 |
| NEC 225, 230, 240, 250, ETC. |
| |
| 3) NOTE: PLEASE SEE RISER WHICH SHOWS TWO BLACK LINES |
| FROM THE GENERATOR. ONE IS SHOWN TO TRANSFER SWITCH AND |
| THE OTHER TO THE TRANSFORMER. WHAT IS THIS SECOND |
| LINE? |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 4) NOTE: PLEASE SEE RISER IS STILL SHOWING EQUIPMENT |
| GROUNDING CONDUCTORS BEFORE THE FIRST MEANS OF |
| DISCONNECT WHICH IS NOT PERMITTED. |
| 250.6, 250.24 |
| |
| ** THERE ARE SEVERAL ITEMS WHICH CAN NOT BE DETERMINED |
| AT THIS TIME. HOWEVER PLEASE SEE THE COMMENTS ABOVE AND |
| PLEASE TAKE A LOOK AT THE PLANS/RISER SUBMITTED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |