Plan Review Notes
Plan Review Notes For Permit 07060173
Permit Number 07060173
Review Stop E
Sequence Number 3
Notes
Date Text
2008-05-30 08:09:57** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SEVERAL NEW COMMENTS ARE NOW BASED ON
 COMPLETELY REVISED ELECTRICAL RISER DIAGRAM WHICH NOW
 CONTAINS SEVERAL NEW CHANGES WHICH WERE NOT PART OF
 PREVIOUSLY SUBMITTED PLANS.
  
 1) NOTE: PLEASE SEE PLANS NOW SHOW A NEW 500KVA
 TRANSFORMER WHICH WAS NOT PART OF PREVIOUS PLANS.
 PLEASE SEE 250.20,250.30 AS THIS IS NOW A SEPARATELY
 DERIVED SYSTEM.
  
 2) NOTE: PLEASE SEE THE TRANSFORMER AS NOTED ABOVE IS
 ALSO SHOWING NEUTRAL CONDUCTORS TO THE TRANSFORMER. HOW
 IS THIS POSSIBLE WHEN THE TRANSFORMER IS SEPARATELY
 DERIVED?
 PLEASE COMPLETE PLANS, CONDUCTORS, RISER, GROUNDING
 ELECTRODE SYSTEM ETC PER 2005 NEC.
 THERE ARE TOO MANY CODE SECTIONS TO NOTE.
 FBC 106.3.5.1.2
 NEC 225, 230, 240, 250, ETC.
  
 3) NOTE: PLEASE SEE RISER WHICH SHOWS TWO BLACK LINES
 FROM THE GENERATOR. ONE IS SHOWN TO TRANSFER SWITCH AND
 THE OTHER TO THE TRANSFORMER. WHAT IS THIS SECOND
 LINE?
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE SEE RISER IS STILL SHOWING EQUIPMENT
 GROUNDING CONDUCTORS BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 250.6, 250.24
  
 ** THERE ARE SEVERAL ITEMS WHICH CAN NOT BE DETERMINED
 AT THIS TIME. HOWEVER PLEASE SEE THE COMMENTS ABOVE AND
 PLEASE TAKE A LOOK AT THE PLANS/RISER SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]