2008-04-07 17:09:38*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1.PLEASE PROVIDE FURTHER DETAILS REGARDING FUEL
 STORAGE TO INCLUDE AMOUNT, LOCATION, AND TANK
 SPECIFICATIONS.
  
 2.PLEASE SHOW LOCATION OF EXHAUST IN RELATION TO ANY
 BUILDING OPENINGS AND MEANS OF EGRESS.
  
 3.WHAT EQUIPMENT WILL BE POWERED BY THE GENERATOR?
  
 4.OK
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722