Plan Review Notes For Permit 07060173 |
Permit Number |
07060173 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-04-07 17:09:38 | *****DENIED***** | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | 1.PLEASE PROVIDE FURTHER DETAILS REGARDING FUEL | | STORAGE TO INCLUDE AMOUNT, LOCATION, AND TANK | | SPECIFICATIONS. | | | | 2.PLEASE SHOW LOCATION OF EXHAUST IN RELATION TO ANY | | BUILDING OPENINGS AND MEANS OF EGRESS. | | | | 3.WHAT EQUIPMENT WILL BE POWERED BY THE GENERATOR? | | | | 4.OK | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|