Plan Review Notes
Plan Review Notes For Permit 07060173
Permit Number 07060173
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-08 17:51:53** DENIED 2NDREVIEW**
  
 ** PLEASE SEE SOME OF THE EXACT SAME COMMENTS FROM
 PREVIOUS REVIEW ARE STILL IN NEED OF ADDRESSING ALONG
 WITH SOME NEW COMMENTS BASED ON NEW PLANS SUBMITTED FOR
 REVIEW.
  
  
 1) NOTE: PLEASE SEE THE PLANS NOW SUBMITTED ARE
 PHOTO-COPIES OF SIGNED, DATED AND SEALED PLANS. PLEASE
 SEE FAC 61G15-23.002 AND FS 471.025 WHICH REQUIRES ALL
 DOCUMENTS TO CONTAIN ORIGINAL SIGNATURES, DATES AND
 RAISED SEALS. THIS IS REQUIRED WHETHER OR NOT COMMENT
 IS MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE THERE ARE STILL NO LOAD
 CALCULATIONS SUBMITTED AS PREVIOUSLY REQUESTED. PLEASE
 SEE NFPA-70 2005 220.87 AND SUBMIT. THE LOADS IN AMPS
 SHOWN ON RISER CAN NOT BE VERIFIED, WHAT IS THE
 VOLTAGE?
 702.5
  
 3) NOTE: PLEASE KNOW A LICENSED CONTRACTOR OTHER THAN
 THE ELECTRICAL CONTRACTOR AS SIGNED ON WILL BE REQUIRED
 FOR STRUCTURAL WORK. EC MAY NOT PERFORM WORK AS SHOWN.
 PLEASE ALSO SEE THE VALUE FOR COMPLETE SCOPE OF WORK
 INCLUDING STRUCTURAL HAS NOT BEEN ADJUSTED.
 PLEASE SEE FBC 108.3.
  
 4) NOTE: PLEASE SEE RISER AS THIS STILL SHOWS AN
 *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED. AS THE CODE
 REQUIRES BONDING AT THE FIRST MEANS OF DISCONNECT ANY
 EQUIPMENT GROUNDING CONDUCTORS INSTALLED BEFORE THE
 FIRST MEANS OF DISCONNECT WOULD PARALLEL THE NEUTRAL
 AND CREATE OBJECTIONABLE CURRENTS.
 PLEASE SEE THE RISER WHICH SHOWS THIS SAME 1/0 AS
 EXISTING WHICH IS NOT POSSIBLE. AS THE INSIDE MSB IS
 NOW AFTER THE FIRST MEANS OF DISCONNECT ONLY NOW WOULD
 THE EQUIPMENT GROUNDING CONDUCTOR BE INSTALLED AND
 NEEDS TO BE SHOWN AS NEW.
 PLEASE ALSO PLACE NOTE ON PLANS AS ALL NEUTRALS AND
 EQUIPMENT GROUNDS WILL BE REQUIRED TO BE SEPARATED IN
 EIXSITNG EQUIPMENT.
 250.24, 250.6
  
 5) NOTE: PLEASE SEE THE RISER DOES NOT SHOW ANY BREAKER
 AT THE GENERATOR AND THE SPECS SUBMITTED DOES NOT
 CLEARLY SHOW A BREAKER OR OVER CURRENT PROTECTION?
 PLEASE KNOW AS NOTED ABOVE FOR LOAD CALCULATIONS, AS
 THE VOLTAGE FOR SYSTEM COULD NOT LOCATED, WE CAN NOT
 DETERMINE SOME ITEMS FOR CODE COMPLIANCE AT THIS TIME.
 240.4, 310.16, 445.13.
  
 6) NOTE: PLEASE SEE THE GENERATOR SPECS INDICATE
 CHARGING FOR BATTERY ETC HOWEVER THE PLANS DO NOT SHOW
 ANY ELECTRICAL FROM SERVICE TO THESE ITEMS.
 BLOCK HEATER? BATTERY CHARGER? ETC
 408.4, 240.4, 310.16, ETC
 PLEASE PROVIDE ADDITIONAL INFORMATION.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]