2008-03-08 17:51:53 | ** DENIED 2NDREVIEW** |
| |
| ** PLEASE SEE SOME OF THE EXACT SAME COMMENTS FROM |
| PREVIOUS REVIEW ARE STILL IN NEED OF ADDRESSING ALONG |
| WITH SOME NEW COMMENTS BASED ON NEW PLANS SUBMITTED FOR |
| REVIEW. |
| |
| |
| 1) NOTE: PLEASE SEE THE PLANS NOW SUBMITTED ARE |
| PHOTO-COPIES OF SIGNED, DATED AND SEALED PLANS. PLEASE |
| SEE FAC 61G15-23.002 AND FS 471.025 WHICH REQUIRES ALL |
| DOCUMENTS TO CONTAIN ORIGINAL SIGNATURES, DATES AND |
| RAISED SEALS. THIS IS REQUIRED WHETHER OR NOT COMMENT |
| IS MADE BY OTHER TRADES. |
| |
| 2) NOTE: PLEASE SEE THERE ARE STILL NO LOAD |
| CALCULATIONS SUBMITTED AS PREVIOUSLY REQUESTED. PLEASE |
| SEE NFPA-70 2005 220.87 AND SUBMIT. THE LOADS IN AMPS |
| SHOWN ON RISER CAN NOT BE VERIFIED, WHAT IS THE |
| VOLTAGE? |
| 702.5 |
| |
| 3) NOTE: PLEASE KNOW A LICENSED CONTRACTOR OTHER THAN |
| THE ELECTRICAL CONTRACTOR AS SIGNED ON WILL BE REQUIRED |
| FOR STRUCTURAL WORK. EC MAY NOT PERFORM WORK AS SHOWN. |
| PLEASE ALSO SEE THE VALUE FOR COMPLETE SCOPE OF WORK |
| INCLUDING STRUCTURAL HAS NOT BEEN ADJUSTED. |
| PLEASE SEE FBC 108.3. |
| |
| 4) NOTE: PLEASE SEE RISER AS THIS STILL SHOWS AN |
| *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS |
| OF DISCONNECT WHICH IS NOT PERMITTED. AS THE CODE |
| REQUIRES BONDING AT THE FIRST MEANS OF DISCONNECT ANY |
| EQUIPMENT GROUNDING CONDUCTORS INSTALLED BEFORE THE |
| FIRST MEANS OF DISCONNECT WOULD PARALLEL THE NEUTRAL |
| AND CREATE OBJECTIONABLE CURRENTS. |
| PLEASE SEE THE RISER WHICH SHOWS THIS SAME 1/0 AS |
| EXISTING WHICH IS NOT POSSIBLE. AS THE INSIDE MSB IS |
| NOW AFTER THE FIRST MEANS OF DISCONNECT ONLY NOW WOULD |
| THE EQUIPMENT GROUNDING CONDUCTOR BE INSTALLED AND |
| NEEDS TO BE SHOWN AS NEW. |
| PLEASE ALSO PLACE NOTE ON PLANS AS ALL NEUTRALS AND |
| EQUIPMENT GROUNDS WILL BE REQUIRED TO BE SEPARATED IN |
| EIXSITNG EQUIPMENT. |
| 250.24, 250.6 |
| |
| 5) NOTE: PLEASE SEE THE RISER DOES NOT SHOW ANY BREAKER |
| AT THE GENERATOR AND THE SPECS SUBMITTED DOES NOT |
| CLEARLY SHOW A BREAKER OR OVER CURRENT PROTECTION? |
| PLEASE KNOW AS NOTED ABOVE FOR LOAD CALCULATIONS, AS |
| THE VOLTAGE FOR SYSTEM COULD NOT LOCATED, WE CAN NOT |
| DETERMINE SOME ITEMS FOR CODE COMPLIANCE AT THIS TIME. |
| 240.4, 310.16, 445.13. |
| |
| 6) NOTE: PLEASE SEE THE GENERATOR SPECS INDICATE |
| CHARGING FOR BATTERY ETC HOWEVER THE PLANS DO NOT SHOW |
| ANY ELECTRICAL FROM SERVICE TO THESE ITEMS. |
| BLOCK HEATER? BATTERY CHARGER? ETC |
| 408.4, 240.4, 310.16, ETC |
| PLEASE PROVIDE ADDITIONAL INFORMATION. |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |