Plan Review Notes
Plan Review Notes For Permit 07060173
Permit Number 07060173
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-02 15:20:57***DENIED***
  
 1) PLEASE PROVIDE FURTHER DETAILS REGARDING FUEL
 STORAGE TO INCLUDE AMOUNT, LOCATION,TANK
 SPECIFICATIONS.
  
 2) PLEASE SHOW LOCATION OF EXHAUST IN RELATION TO ANY
 BUILDING OPENINGS AND MEANS OF EGRESS.
  
 3) WHAT EQUIPMENT WILL BE POWERED BY GENERATOR?
  
 4) WORK SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756