2007-07-26 10:13:59BUILDING REVISION CHECKLIST:
 1- ROOF VENT:
 A) ARCHITECT APPROVED ROOF VENT NOA 01-0614.05. THIS
 NOA EXPIRED ON 08/16/2006.DADE COUNTY NOA'S SHALL
 NOT BE VALID AFTER EXPIRATION DATE.SEE SECOND
 PARAGRAPH ON COVER PAGE OF NOA SUBMITTED.
  
 B)ARCHITECT'S NOTE: "CONTRACTOR RESPONSIBLE FOR
 PROVIDING REQ'D VENTING PER CALCULATIONS ON DRAWINGS".
 IT'S THE ARCHITECT'S RESPONSIBILITY TO VERIFY IFTHE
 NUMBER OFVENTS SHOWN ON PLANSMEET THE VENTING
 CALCULATIONS USING THE REVISED VENT,NOT THE
 CONTRACTOR.CONTRACTOR'SRESPONSIBILITYIS TO
 INSTALLNUMBER OF VENTS VENTSAS SPECIFIED ON PLANS.
 NOT TO MAKE CALCULATIONS.IF REVISEDVENT DOESN'T
 MEET THE VENTING CALCULATIONS, THEN REVISE PLANS AS
 REQUIRED.
  
 C) THERE ARE TWO DIFFERENT REVIEW STAMPS. ONE OF
 THEM IS CLEAR THAT IS THE ARCHITECT'S REVIEW STAMP.
 WHO'S REVIEW STAMP IS THE OTHER ONE.THE PURPOSE OF
 THE REVIEW STAMP IS TO DISCLOSE WHO REVIEW IT.
 OTHERWISE IT'S MEANINGLESS.
  
 ***NOTE: SAME COMMENT APPLIES TO SHINGLES PRODUCT
 APPROVAL.
  
 2- REVISION FEES ARE $50.00PLUS $10.00 PER ADDITIONAL
 PAGE. OWES $20.00.INFORMATION SUBMITTED IS REVISED
 SHEET A705, PLUS PRODUCT APPROVAL FOR SHINGLES, PLUS
 PRODUCT APPROVAL FOR ROOF VENT.
  
 3- PRODUCT APPROVAL FOR ROOF SHINGLES HAS THE
 ARCHITECT'S REVIEW STAMP, BUT NOBODY SIGNED IT AND
 DATED IT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER