2007-06-21 18:58:30 | PLACED ON BOB BOARD ON 6/21 |
2007-06-21 18:48:57 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE 13-103, 13-415.1.1, .1.2 AS THE NEW |
| SWITCHING DEVICES INSTALLED OR REPLACED MUST COMPLY |
| WITH CHAPTER 13 OF THE FBC 2004 W/ 2006 REVISIONS. |
| |
| 2) NOTE: PLEASE SEE DEVICES ON PLANS WHICH ARE BEING |
| SHOWN AS *E* FOR EXISTING YET THIS CAN NOT BE POSSIBLE |
| WHEN THE DEMO AND ARCHITECTURAL PLANS DO NOT SHOW THESE |
| WALLS YET? |
| PLEASE COORDINATE THESE ITEMS. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 3) NOTE: PLEASE SEE 408.4 AS THE CIRCUITING ON PANEL |
| SCHEDULE NEEDS TO BE SPECIFIC TO ALL ROOMS AND AREAS IN |
| WHICH THEY FEED. |
| 4) NOTE: PLEASE CLARIFY CONDUCTOR SIZES ON NEW CIRCUITS |
| ON PANEL. CAN BE TYPICAL IF ALL ARE THE SAME. 240.4, |
| 310.16. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 5) NOTE: PLEASE CLARIFY NOT ON RISER FOR WHAT APPEARS |
| TO BE A NEW PANEL ON SECONDARY SIDE OF THE TRANSFORMER. |
| PLEASE SEE NOTES MENTIONS *MUST HAVE MCB WITH 100AMP |
| OCP*. YET THE SENTENCE JUST FOLLOWING STATES *INSTALL |
| IF REQUIRED*. IT IS UNCLEAR WHAT IS MEANT. |
| PLEASE SEE THE CODE IS SPECIFIC IN 408.36 AND 240.21 |
| THAT A MAIN OF SOME TYPE IS REQUIRED IN |
| LIGHTING/APPLIANCE PANEL BOARDS AND ALSO MUST TERMINATE |
| IN OCP BECAUSE OF TAPPED CONDUCTORS ON THE SECONDARY |
| SIDE OF THE TRANSFORMER. |
| ** PLEASE ADJUST NOTE. |
| |
| 6) NOTE: PLEASE CLARIFY CD LEVELS FOR ADA OF STROBES |
| PER FBC 11-4.28.3(4). |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |