Plan Review Notes
Plan Review Notes For Permit 07060104
Permit Number 07060104
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-13 14:48:51*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED.
  
 2.IN JUNE 4,2007 CORRESPONDENCE THAT WAS SUBMITTED,
 NFPA 101, 7.2.1.5.2 IS REFERENCED.PLEASE EXPLAIN HOW
 THIS REFERS TO THE PROPOSED SCOPE OF WORK.
  
 3.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM AS PER 2003 NFPA 101, 7.2.1.6.2
  
 4.CITY AMENDMENT 104.2.1.ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 5.SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A
 COPY THEREOF.
  
 6.SINCE THE SCOPE OF THE WORK IS GREATER THAN
 $5,000.00, AS PER FLORIDA ADMINISTRATIVE CODES, A
 PROFESSIONAL ENGINEER SHALL SIGN HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, ETC TO BE FILED FOR PUBLIC RECORD. THE
 STAMPED ENGINEERED SEAL SHALL HAVE THE WORDING
 "LICENSE" IN LIEU OF "CERTIFICATE".
  
 7.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
  
 CAPT.MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW