2007-06-19 07:49:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)SHUTTER MOUNTING CONNECTION TYPE SHOULD REFER TO
 CONNECTIONS C1 THROUGH C5.
  
 2.)SEE OPENING 4 , F/B IS SPECIFIED, 12" SPACING.
 DETAIL B, SHEET 5 OF THE PRODUCT APPROVAL USES C4
 CONNECTION TYPE.C4 REQUIRES 8" SPACING, SEE THE
 SCHEDULE ON SHEET 8.PLEASE CHECK ALL OPENINGS.