2007-06-10 12:21:49 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE THE MINOR MISPRINT FOR CODE ON |
| FRONT SHEETS. SHOWS BOTH THE 2005 NFPA_70 AND THE 2002 |
| NEC. |
| |
| 2) NOTE: PLEASE SEE SHEET A-3 WHICH MENTIONS NEW DEVICE |
| FOR AUTO-SHUT OFF PER CHAPTER 13, HOWEVER PLEASE |
| ELABORATE ON DEVICE FOR TYPE. IS THIS ULTRASONIC? IF |
| ONLY MOTION, THEN WALL/STALL PARTITIONS WILL NOT |
| PROVIDE NEEDED COVERAGE. |
| PLEASE ALSO STATE MAXIMUM TIME FOR DEVICE. |
| 13-415.1.ABC.1.1 |
| |
| 3) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP |
| OF SOME TYPE FOR EACH RESTROOM PER LS 101 7.8, 7.9 |
| WIRED TO LOCAL LIGHTING CIRCUIT PER 700.12F OF THE 2005 |
| NEC> |
| |