2007-06-19 12:11:49BUILDING PLAN REVIEW
 PERMIT:07060050
 ADD:560 VILLAGE BLVD
 CONT:FISHER CONTRACTING CORP
 TEL: (561)619-4716
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) THIS A LEVEL 2 ALTERATION.FLORIDA EXISTING
 BUILDING CODE. SEC.304.1 : LEVEL 2 ALTERATION INCLUDE
 THE RECONFIGURATION OF SPACE, THE ADDITION OR
 ELIMINIATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION
 OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT.
  
 3)FBC. 11-4.17EXCEPTION: NEW CONSTRUCTION.
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726