2007-07-02 18:06:06 | PROJECT: 800 45TH STREET |
| |
| PROJECT WORK SCOPE: REMOVE EXISTING SCREEN ENCLOSURE/ |
| CONSTRUCT BEDROOM & BATH |
| |
| PLAN REVIEW: 2004 FLORIDA EXISTING BUILDING CODE AND |
| FLORIDA BUILDING CODE WITH 2006 REVISIONS. |
| |
| STATUS: DENIED |
| |
| |
| PLAN REVIEW COMMENTS: |
| |
| 1)105.8 NOTICE OF COMMENCEMENT. |
| AS PER SECTION 713.135, FLORIDA STATUTES, WHEN ANY |
| PERSON APPLIES FOR A BUILDING PERMIT, THE AUTHORITY |
| ISSUING SUCH PERMIT SHALL PRINT ON THE FACE OF EACH |
| PERMIT CARD IN NO LESS THAN 18-POINT, CAPITALIZED, |
| BOLDFACED TYPE:?WARNING TO OWNER: YOUR FAILURE TO |
| RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR |
| PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU |
| INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR |
| AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF |
| COMMENCEMENT.? |
| |
| 2) INITIAL AND SIGN THE OWNER BUILDER INFORMATION |
| FORM. |
| |
| 3) PROVIDE SUPPORTING DOCUMENTATION VERIFYING THE |
| EXISTING SIZE OF THE MONOLITHIC FOUNDATION AND |
| REINFORCING STEEL PLACEMENT. INDICATE CONCRETE |
| SPECIFICATIONS OF NEW FLOOR SLAB OVERLAY. |
| |
| 4) PLEASE PROVIDE PRODUCT APPROVALS AND SPECIFICATIONS |
| FOR ALL MECHANICAL CONNECTORS AND ANCHORS TO BE |
| UTILIZED. |
| |
| 5) PLEASE INDICATE SPECIES AND GRADE OF LUMBER. |
| |
| 6) PROVIDE THE FOLLOWING INFORMATION: |
| |
| A) WINDOW TYPE AND GLAZING SPECS. |
| B) DOOR SPECIFICATIONS/ DESIGN PRESSURE. |
| C) NEW DOOR AT PLAYROOM SHOWS A WINDOW. THE |
| SUBMITTED PRODUCT APPROVAL DOES NOT REFLECT THE SAME. |
| D) REQUIRE 2 COPIES OF DOOR AND WINDOW PRODUCT |
| APPROVALS. |
| |
| |
| 7) THE OBS WINDOW AT THE BATHROOM SHALL BE SAFETY |
| TEMPERED GLAZING AS PER THE FOLLOWING: |
| |
| 2406.3 HAZARDOUS LOCATIONS. |
| THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS |
| LOCATIONS REQUIRING SAFETY GLAZING MATERIALS: |
| |
| 5. GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, |
| WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS. |
| GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING |
| THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE |
| GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A |
| STANDING SURFACE. |
| |
| 8) PLEASE SHOW ALL EXTERIOR ELEVATIONS. |
| |
| 9) SMOKE ALARMS SHALL BE INSTALLED PER THE FOLLOWING: |
| |
| 604.4.3SMOKE ALARMS. |
| INDIVIDUAL SLEEPING UNITS AND INDIVIDUAL DWELLING UNITS |
| IN ANY WORK AREA IN GROUP R-1, R-2, R-3, R-4, AND I-1 |
| OCCUPANCIES SHALL BE PROVIDED WITH SMOKE ALARMS IN |
| ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| EXCEPTION: INTERCONNECTION OF SMOKE ALARMS OUTSIDE OF |
| THE REHABILITATION WORK AREA SHALL NOT BE REQUIRED. |
| |
| 10) PLEASE SHOW AN INTERIOR WALL FRAMING SECTION. |
| |
| 11) ALL OPENINGS SHALL BE PROTECTED. PLEASE PROVIDE |
| SHUTTER PRODUCT APPROVALS. |
| |
| 1609.1.4 PROTECTION OF OPENINGS. |
| IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT |
| RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 |
| M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE |
| BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING |
| SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, |
| ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING DOORS) OR |
| MIAMI-DADE TAS 201, 202 AND 203 OR AAMA 506 REFERENCED |
| THEREIN AS FOLLOWS: |
| 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF |
| GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE |
| TEST. |
| 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| MISSILE TEST. |
| 3. STORAGE SHEDS THAT ARE NOT DESIGNED FOR HUMAN |
| HABITATION AND THAT HAVE A FLOOR AREA OF 720 SQUARE |
| FEET (67 M2) OR LESS ARE NOT REQUIRED TO COMPLY WITH |
| THE MANDATORY WINDBORNE DEBRIS IMPACT STANDARDS OF THIS |
| CODE. |
| 4. OPENINGS IN SUNROOMS, BALCONIES OR ENCLOSED PORCHES |
| CONSTRUCTED UNDER EXISTING ROOFS OR DECKS ARE NOT |
| REQUIRED TO BE PROTECTED PROVIDED THE SPACES ARE |
| SEPARATED FROM THE BUILDING INTERIOR BY A WALL AND ALL |
| OPENINGS IN THE SEPARATING WALL ARE PROTECTED IN |
| ACCORDANCE WITH SECTION 1609.1.4 ABOVE. SUCH SPACES |
| SHALL BE PERMITTED TO BE DESIGNED AS EITHER PARTIALLY |
| ENCLOSED OR ENCLOSED STRUCTURES. |
| |
| 12) THE PROPOSED CONSTRUCTION VALUE APPEARS TO BE LOW |
| AS PER THE MARSHAL AND SWIFT COST ESTIMATION. |
| |
| PLAN REVIEW: KEN CONRAD |
| |