2007-06-15 08:21:23*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 2) PLEASE BE AWARE. PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED EQUIPMENT POWERED BY
 INTERNAL COMBUSTION ENGINES SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS)
 LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS
 IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING
 COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED
 WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE ENCLOSURE WILL
 NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT
 TERMINATE UNDER STRUCTURES OR WHERE THE EXHAUST MIGHT
 BE DRAWN INTO THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED
 BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT
 TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES
 TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE, BUILDING, WINDOWS,
 DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND
 EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE FOR THE FIELD
 INSPECTOR.