Plan Review Notes For Permit 07051008 |
Permit Number |
07051008 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-06-28 16:49:29 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.)ANCHOR SPACING ON THE CHARTS IS FOR 3 1/2" EDGE | | DISTANCE.ON THE INSTALLATION SCHEDULE, YOU'VE | | SPECIFIED 3", WHICH REQUIRES A FACTOR OF .83.SEE | | OPENINGS 6 AND 7, WALL MOUNT 4, 10" SPECIFIED BUT THAT | | SHOULD BE MULTIPLIED BY .83 FOR CORRECT ANCHOR | | SPACING. | | |
|