Plan Review Notes
Plan Review Notes For Permit 07050998
Permit Number 07050998
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-22 08:46:16*** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED WHICH ARE RUN THROUGH THE FLA/COM PROJECT MAY
 NOT BE ALTERED BY TYPING IN INFORMATION ETC BY HAND.
 PLEASE ALSO SEE THAT THE DESIGN WATTAGE IS BEING SHOWN
 MUCH HIGHER THAN THE EFFECTIVE OR ALLOWANCE WATTAGE.
 HOW IS THIS POSSIBLE?
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS, THESE
 MAY BE ON THE PLANS SET UP IN SOME SORT OF TABLE FORM.
 RESPONSE LETTER MENTIONS THIS WAS DONE PER 13-415.2.B,
 PLEASE SHOW THIS ON PLANS.
  
 ** PLEASE CALL TO GO OVER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]