2007-10-22 08:46:16 | *** DENIED 3RD REVIEW *** | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING. | | | | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS | | SUBMITTED WHICH ARE RUN THROUGH THE FLA/COM PROJECT MAY | | NOT BE ALTERED BY TYPING IN INFORMATION ETC BY HAND. | | PLEASE ALSO SEE THAT THE DESIGN WATTAGE IS BEING SHOWN | | MUCH HIGHER THAN THE EFFECTIVE OR ALLOWANCE WATTAGE. | | HOW IS THIS POSSIBLE? | | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS, THESE | | MAY BE ON THE PLANS SET UP IN SOME SORT OF TABLE FORM. | | RESPONSE LETTER MENTIONS THIS WAS DONE PER 13-415.2.B, | | PLEASE SHOW THIS ON PLANS. | | | | ** PLEASE CALL TO GO OVER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-10-22 08:06:17 | 2007-10-22 08:06:17 | | | | IN PROGRESS |
|