2007-09-07 18:52:12 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| |
| |
| 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. |
| THE RESPONSE MENTIONS THIS WAS UPDATED ON SHEET A-0.1 |
| HOWEVER IT WAS ASKED FOR THE RELEVANT CODES TO BE |
| PLACED ON ELECTRICAL SHEETS HOWEVER THIS WAS NOT DONE. |
| PLANS ONLY STATE THE *LATEST ADOPTED CODES*. |
| AS PLANS ARE COMING BACK FOR OTHER COMMENTS AND |
| CORRECTION PLEASE INCLUDE ON ELECTRICAL PLANS. |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE BE SURE TO STATE ALL THE RELEVANT CODES AS |
| ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH, |
| 2006. |
| PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED. |
| SOME CODES STATED NEVER EXISTED.(2003 NEC) |
| |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON |
| ELECTRICAL SHEETS) |
| 2002 NFPA-72 |
| |
| ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER |
| TRADES. |
| |
| 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| FOR THE ARCHITECTURAL FIRM ON E-SHEETS. AS THESE SHEET |
| ARE BEING CORRECTED FOR OTHER COMMENTS, PLEASE SEE THE |
| PRINTED FIRM CERTIFICATE OF AUTHORIZATION NUMBER IS THE |
| ONLY ITEM THAT IS MISSING. 61G1-16.004 FOR ARCHITECT |
| FIRM. |
| |
| ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE |
| REVIEWER(S). |
| |
| 3) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE |
| FBC HAS NOT BEEN MET. |
| PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ONCE |
| AGAIN DO NOT CORRELATE WITH PLANS OR THE FIXTURE LEGEND |
| AS SUBMITTED. PLEASE SEE THERE ARE IN FACT SEVERAL HAND |
| PRINTED ITEMS ON THE INPUT DATA REPORT WHICH MUST BE |
| PLACED INTO THE IDR WHEN RUNNING REPORT. |
| PLEASE CORRELATE. |
| PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH. |
| PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH. |
| PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH. |
| PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK |
| LIGHTING CALCULATIONS AND FIGURES. |
| ** PLEASE SEE THE FBC 13-415.1.B.1.1, 13-415.2 AND |
| TABLES FOR METHOD *B*. |
| PLEASE SEE THE REQUIRED LIGHTING CONTROLS ARE NOT |
| SHOWN ON PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2. |
| PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING |
| CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE |
| DEVICE TIMES. |
| PLEASE PROVIDE MORE INFORMATION/DETAIL FOR THE TIME |
| CLOCK BEING NOTED. |
| AT THIS TIME. |
| |
| 4) NOTE: PLEASE SEE NOTE #10 ON SHEET E-2.0 MENTIONS |
| THE FIRE ALARM PANEL IS TO BE CIRCUITED TO PANEL *A* |
| 41, YET THIS SPACE IS BEING SHOWN AS SPARE? |
| PLEASE COORDINATE. |
| FBC 106.3.5.1.2, 106.1.2 |
| NEC 408.4. |
| |
| 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE |
| FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST |
| SERVICE CALCULATIONS. |
| RESPONSE MENTIONS TO REFER TO REVISED CALCULATIONS |
| HOWEVER HOW THE SHOW WINDOW LOAD WAS DERIVED OR SHOWN |
| IN THESE CALCULATIONS IS NOT CLEAR. |
| |
| 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| NOTICE GIVEN AT THIS TIME. |
| TWO SETS OF ELECTRICAL PLANS AND ENERGY CALCULATIONS |
| ARE BEING RETAINED BY THIS OFFICE. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** AS STATED IN THE PREVIOUS REVIEW,: |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |