2007-09-11 08:22:47 | BUILDING PLAN REVIEW |
| PERMIT: 07050998 |
| ADD: 550 S.ROSEMARY AVE |
| CONT: RCC ASSOCIATES, INC. |
| TEL: (954)429-3700 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 2ND |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2)F.A.C. 61G15-23.002ENGINEERS SHALL LEGIBLY |
| INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON |
| EACH SHEET, IF PRACTICING THROUGH A DULY AUTHORIZED |
| ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME, |
| ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| ENGINEERING BUSINESS ON EACH SHEET. SEE 61G1-16.004 / |
| F.S. 471.023 / 481.219. |
| **THE NEW ARCHITECTURAL SHEETS ARE MISSING THE SEAL OF |
| THE ARCHITECT AND THE DATE WHICH THEY WERE SEALED. ONE |
| SET OF NEW PLANS IS MISSING THE ELECTRICAL SHEETS. OUR |
| OFFICE SHALL RETAIN ON SET AS PROOF THE PLANS WERE NOT |
| SEALED. |
| |
| 3)INDICATE HOW WALL DETAIL # 2 ON SHEET A-4.0 WILL BE |
| ATTATCH TO THE EXISTING STRUCTURE? |
| |
| 4)OK |
| |
| 5)OK |
| |
| 6)OK |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |
| [email protected]. |