Plan Review Notes
Plan Review Notes For Permit 07050998
Permit Number 07050998
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-23 15:30:42--------------------DENIED---------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
  
 1. PG A-0.1: PLEASE REFERENCE FLORIDA BUILDING CODE,
 MECHANICAL 2004 ON PLANS.
  
 2. THE ENGINEER'S PRINTED NAME AND LICENCE NUMBER,
 ALONG WITH ENGINEERING FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER ARE REQUIRED ON EACH PAGE FOR
 WHICH THE ENGINEER IS RESPONSIBLE PER FAC RULE
 61G15-23.002
  
 3. AIR BALANCE AS SHOWN ON PLAN IS AT -20 CFM.
 MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT
 BUILDINGS ARE PRESSURIZED WITH RESPECT TO THE OUTDOORS
 PER FBC 13-409.1.ABC.2
  