2007-07-10 17:31:38*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS, INCLUDING THE TENANT SPACE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2.NFPA 101, THE LIFE SAFETY CODE, 2003 EDITION SHALL
 BE REFERENCED.AMEND APPLICABLE CODE ON SHEET A-01.
  
 3.CONSTRUCTION/DEMOLITION OPERATIONS AND/OR THE
 PLACEMENT OF THE DUMPSTER SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS RESPONSE TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 4.DECLARE INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5.INDICATE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  