Plan Review Notes
Plan Review Notes For Permit 07050998
Permit Number 07050998
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-20 21:03:50*** UNSAT***
  
  
 1) NOTE: PLEASE BE SURE TO STATE ALL THE RELEVANT CODES
 AS ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED.
 SOME CODES STATED NEVER EXISTED.(2003 NEC)
  
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON
 ELECTRICAL SHEETS)
 2002 NFPA-72
  
 ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR BOTH THE ARCHITECT, FIRM AS WELL AS THE ENGINEER
 AND ENGINEERING FIRM.
 PLEASE SEE MISSING THE PRINTED NAMES FOR DESIGNERS.
 PLEASE SEE THE PRINTED LICENSE NUMBERS FOR DESIGNERS.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBERS FOR BOTH FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 FOR
 ENGINEERS AND 61G1-16.004 FOR ARCHITECT FIRM.. PLEASE
 SEE FLORIDA STATUTES 471.023 FOR ENGINEERS AND 481.219
 FOR ARCHITECT FIRM.
  
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE
 REVIEWER(S).
  
 2) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE
 FBC HAS NOT BEEN MET.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE
 NOTE SEALED BY THE DESIGNER OF RECORD. PLEASE BE SURE
 TO SIGN, DATE AND SEAL CALCULATIONS.
 13-103.1.1.1
 ** PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON
 SECOND SHEET AS REQUIRED.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT
 CORRELATE WITH PLANS.
 PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH.
 PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH
 PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH.
 PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK LIGHTING
 CALCULATIONS AND FIGURES.
 ** PLEASE SEE THE FBC 13-415.1.AB.1.1, 13-415.2 AND
 TABLES FOR METHOD *B*. PLEASE VERIFY METHOD *B*. PLEASE
 SEE THE REQUIRED LIGHTING CONTROLS ARE NOT SHOWN ON
 PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING
 CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE
 DEVICE TIMES.
 PLEASE SEE OF OCCUPANCY SENSOR TYPE DEVICES ARE USED,
 PLEASE LIST THE MAXIMUM TIMES PER SECTIONS ABOVE. IF
 TIMER TYPE DEVICES ARE USED PLEASE LIST MAXIMUM
 TIMES.(4HRS).
 ** AS DESIGNS WERE NOT SHOWN ON PLANS FOR REVIEW A
 COMPLETE REVIEW OF THESE ITEMS CAN NOT BE DONE AT THIS
 TIME.
  
 3) NOTE: PLEASE SEE ELECTRICAL EQUIPMENT IS BEING NOTED
 IN STORAGE ROOM WHICH IS NOT PERMITTED. PLEASE SEE
 110.26, 408.7, 240.24 ETC.
 THIS MAY NOT BE STORAGE ROOM.
  
 4) NOTE: PLEASE SEE RISER SHOWS A NEW PANEL ON THE
 SECONDARY SIDE OF THE TRANSFORMER HOWEVER THE NOTE ON
 THE RISER MENTIONS EXISTING CONDUCTORS TO REMAIN. AS
 THE EXISTING PANEL, MAIN CIRCUIT BREAKER SIZE AND
 CONDUCTORS WAS NOT GIVEN IT CAN NOT BE DETERMINED IF
 THE EXISTING CONDUCTORS ARE OF SUFFICIENT SIZE TO
 TERMINATE IN THE 100AMP BREAKER AS SHOWN ON NEW PANEL.
 PLEASE SEE 240.21, 310.16, 240.4.
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE
 FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST
 SERVICE CALCULATIONS.
  
 6) NOTE: PLEASE SEE THE EMERGENCY AND EXIT LIGHTS SHALL
 BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN THAT AREA.
 PLEASE SEE 700.12F.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS