2007-06-20 21:03:50 | *** UNSAT*** |
| |
| |
| 1) NOTE: PLEASE BE SURE TO STATE ALL THE RELEVANT CODES |
| AS ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH, |
| 2006. |
| PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED. |
| SOME CODES STATED NEVER EXISTED.(2003 NEC) |
| |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON |
| ELECTRICAL SHEETS) |
| 2002 NFPA-72 |
| |
| ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER |
| TRADES. |
| |
| 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| FOR BOTH THE ARCHITECT, FIRM AS WELL AS THE ENGINEER |
| AND ENGINEERING FIRM. |
| PLEASE SEE MISSING THE PRINTED NAMES FOR DESIGNERS. |
| PLEASE SEE THE PRINTED LICENSE NUMBERS FOR DESIGNERS. |
| PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| NUMBERS FOR BOTH FIRMS. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 FOR |
| ENGINEERS AND 61G1-16.004 FOR ARCHITECT FIRM.. PLEASE |
| SEE FLORIDA STATUTES 471.023 FOR ENGINEERS AND 481.219 |
| FOR ARCHITECT FIRM. |
| |
| ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE |
| REVIEWER(S). |
| |
| 2) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE |
| FBC HAS NOT BEEN MET. |
| PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE |
| NOTE SEALED BY THE DESIGNER OF RECORD. PLEASE BE SURE |
| TO SIGN, DATE AND SEAL CALCULATIONS. |
| 13-103.1.1.1 |
| ** PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON |
| SECOND SHEET AS REQUIRED. |
| PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT |
| CORRELATE WITH PLANS. |
| PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH. |
| PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH |
| PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH. |
| PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK LIGHTING |
| CALCULATIONS AND FIGURES. |
| ** PLEASE SEE THE FBC 13-415.1.AB.1.1, 13-415.2 AND |
| TABLES FOR METHOD *B*. PLEASE VERIFY METHOD *B*. PLEASE |
| SEE THE REQUIRED LIGHTING CONTROLS ARE NOT SHOWN ON |
| PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING |
| CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE |
| DEVICE TIMES. |
| PLEASE SEE OF OCCUPANCY SENSOR TYPE DEVICES ARE USED, |
| PLEASE LIST THE MAXIMUM TIMES PER SECTIONS ABOVE. IF |
| TIMER TYPE DEVICES ARE USED PLEASE LIST MAXIMUM |
| TIMES.(4HRS). |
| ** AS DESIGNS WERE NOT SHOWN ON PLANS FOR REVIEW A |
| COMPLETE REVIEW OF THESE ITEMS CAN NOT BE DONE AT THIS |
| TIME. |
| |
| 3) NOTE: PLEASE SEE ELECTRICAL EQUIPMENT IS BEING NOTED |
| IN STORAGE ROOM WHICH IS NOT PERMITTED. PLEASE SEE |
| 110.26, 408.7, 240.24 ETC. |
| THIS MAY NOT BE STORAGE ROOM. |
| |
| 4) NOTE: PLEASE SEE RISER SHOWS A NEW PANEL ON THE |
| SECONDARY SIDE OF THE TRANSFORMER HOWEVER THE NOTE ON |
| THE RISER MENTIONS EXISTING CONDUCTORS TO REMAIN. AS |
| THE EXISTING PANEL, MAIN CIRCUIT BREAKER SIZE AND |
| CONDUCTORS WAS NOT GIVEN IT CAN NOT BE DETERMINED IF |
| THE EXISTING CONDUCTORS ARE OF SUFFICIENT SIZE TO |
| TERMINATE IN THE 100AMP BREAKER AS SHOWN ON NEW PANEL. |
| PLEASE SEE 240.21, 310.16, 240.4. |
| PLEASE PROVIDE MORE INFORMATION. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE |
| FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST |
| SERVICE CALCULATIONS. |
| |
| 6) NOTE: PLEASE SEE THE EMERGENCY AND EXIT LIGHTS SHALL |
| BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN THAT AREA. |
| PLEASE SEE 700.12F. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |