Plan Review Notes For Permit 07050984 |
Permit Number |
07050984 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-04 18:28:22 | PLANS EXAMINER: KEN CONRAD | | 3814 SHELLY ROAD | | #07050984 | | | | APPLICABLE CODE: 2004 FLORIDA EXISTING BUILDING CODE | | | | DENIED: SEE BELOW. | | | | | | A PRELIMINARY INSPECTION WAS PERFORMED. THE FOLLOWING | | WAS NOTED: | | | | 1) REQUIRE TWO COPIES OF THE STATE AND LOCAL PRODUCT | | APPROVALS FOR THE ROOF TILE. | | 2) DUE TO THE INTENDED SCOPE OF THE ROOF REPAIR | | ENCOMPASSING 30% OF THE ROOF, THE WORK SHALL COMPLY TO | | THE PROVISIONS OF FEBC 511.1.2. | | | | 511.1GENERAL. | | MATERIALS AND METHODS OF APPLICATION USED FOR | | RECOVERING OR REPLACING AN EXISTING ROOF COVERING SHALL | | COMPLY WITH THE REQUIREMENTS OF CHAPTER 15 OF THE | | FLORIDA BUILDING CODE, BUILDING. ROOF REPAIRS TO | | EXISTING ROOFS AND ROOF COVERINGS SHALL COMPLY WITH THE | | PROVISIONS OF THIS CODE. | | | | 511.1.2 | | NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF | | SECTION OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE | | REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD | | UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION | | CONFORMS TO REQUIREMENTS OF THIS CODE. | | | | 511.2STRUCTURAL AND CONSTRUCTION LOADS. | | THE STRUCTURAL ROOF COMPONENTS SHALL BE CAPABLE OF | | SUPPORTING THE ROOF COVERING SYSTEM AND THE MATERIAL | | AND EQUIPMENT LOADS THAT WILL BE ENCOUNTERED DURING | | INSTALLATION OF THE ROOF COVERING SYSTEM |
|