Plan Review Notes
Plan Review Notes For Permit 07050984
Permit Number 07050984
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-04 18:28:22PLANS EXAMINER: KEN CONRAD
 3814 SHELLY ROAD
 #07050984
  
 APPLICABLE CODE: 2004 FLORIDA EXISTING BUILDING CODE
  
 DENIED: SEE BELOW.
  
  
 A PRELIMINARY INSPECTION WAS PERFORMED. THE FOLLOWING
 WAS NOTED:
  
 1) REQUIRE TWO COPIES OF THE STATE AND LOCAL PRODUCT
 APPROVALS FOR THE ROOF TILE.
 2) DUE TO THE INTENDED SCOPE OF THE ROOF REPAIR
 ENCOMPASSING 30% OF THE ROOF, THE WORK SHALL COMPLY TO
 THE PROVISIONS OF FEBC 511.1.2.
  
 511.1GENERAL.
 MATERIALS AND METHODS OF APPLICATION USED FOR
 RECOVERING OR REPLACING AN EXISTING ROOF COVERING SHALL
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 15 OF THE
 FLORIDA BUILDING CODE, BUILDING. ROOF REPAIRS TO
 EXISTING ROOFS AND ROOF COVERINGS SHALL COMPLY WITH THE
 PROVISIONS OF THIS CODE.
  
 511.1.2
 NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF
 SECTION OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE
 REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD
 UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION
 CONFORMS TO REQUIREMENTS OF THIS CODE.
  
 511.2STRUCTURAL AND CONSTRUCTION LOADS.
 THE STRUCTURAL ROOF COMPONENTS SHALL BE CAPABLE OF
 SUPPORTING THE ROOF COVERING SYSTEM AND THE MATERIAL
 AND EQUIPMENT LOADS THAT WILL BE ENCOUNTERED DURING
 INSTALLATION OF THE ROOF COVERING SYSTEM