2007-06-27 08:11:55 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY |
| OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| |
| FROM PREVIOUS LIST: |
| |
| _XX_2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN |
| PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE |
| DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A |
| DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER |
| AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| ORIGINALS FAC61G15-23.002. |
| |
| 2ND REVIEW - ORIGINALS REQUIRED.ONE WAS A PHOTOCOPY. |
| |
| |
| _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE |
| OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| ANOTHER FORMAT. |
| |
| 2ND REVIEW - A SIMILAR FORM WAS SUBMITTED BUT DOES NOT |
| INLUDE SHUTTER MOUNTING TYPE.CODE COMPLIANCE CANNOT |
| BE DETERMINED. |
| |
| _XX_5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.THE FL |
| STATE PRODUCT APPROVAL IS EXPIRED, 2001 CODE RATHER |
| THAN 2004.PLEASE PRINT A CURRENT APPROVAL.IF ONE IS |
| NOT AVAILABLE, PLEASE ADVISE. |
| |
| 2ND REVIEW - NOT ADDRESSED.IN ORDER FOR A LOCAL |
| PRODUCT APPROVAL TO BE ISSUED, PLEASE SUBMIT THE LETTER |
| FROM THE ENGINEER WHICH WAS PROVIDED TO MIAMIDADE |
| STATING THAT THE CALCULATIONS ARE IN ACCORDANCE WITH |
| FBC2004.NO 33% INCREASE FOR STEEL ALLOWED. |
| |