2007-06-27 08:11:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST:
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 2ND REVIEW - ORIGINALS REQUIRED.ONE WAS A PHOTOCOPY.
  
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 2ND REVIEW - A SIMILAR FORM WAS SUBMITTED BUT DOES NOT
 INLUDE SHUTTER MOUNTING TYPE.CODE COMPLIANCE CANNOT
 BE DETERMINED.
  
 _XX_5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.THE FL
 STATE PRODUCT APPROVAL IS EXPIRED, 2001 CODE RATHER
 THAN 2004.PLEASE PRINT A CURRENT APPROVAL.IF ONE IS
 NOT AVAILABLE, PLEASE ADVISE.
  
 2ND REVIEW - NOT ADDRESSED.IN ORDER FOR A LOCAL
 PRODUCT APPROVAL TO BE ISSUED, PLEASE SUBMIT THE LETTER
 FROM THE ENGINEER WHICH WAS PROVIDED TO MIAMIDADE
 STATING THAT THE CALCULATIONS ARE IN ACCORDANCE WITH
 FBC2004.NO 33% INCREASE FOR STEEL ALLOWED.
  