Plan Review Notes
Plan Review Notes For Permit 07050962
Permit Number 07050962
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-13 18:41:39 
  
 DENIED
  
 1)IF THE GLASS BLOCK IS NO LONGER BEING USED AS THE
 MASTER BATH ROOM WINDOW PLEASE REMOVE FROM THE
 DRAWINGS. IF ANOTHER WINDOW IS TO BE INSTALLED SHOW
 SIZE AND STATE THAT SAFETY GLAZING WILL BE USED.
  
 2)THE PRODUCT APPROVAL FOR THE ENTRY DOORS MEETS THE
 DESIGN PRESSURE (-47.2 PSF) REQUIRED ON SHEET 2 OF THE
 DRAWINGS FOR THE SINGLE DOORS BUT NOT THE DOUBLE SET AT
 THE REAR, THE PRODUCT APPROVAL IS ONLY GOOD UP TO -45
 PSF
  
 3)THE PRODUCT APPROVAL FOR THE GARAGE DOOR IS FOR A
 COMMERCIAL ROLL UP TYPE, IS THIS SLAT TYPE DOOR THE
 TYPE YOU WISH TO INSTALL IF SO THE PROBLEM IS THE SAME
 AS COMMENT NUMBER 2, PRODUCT APPROVAL GOOD TO -34 PSF
 AND SHEET 2 OF DRAWINGS HAS A DESIGN PRESSURE OF -39.8
 PSF
  
 4)THE ENERGY CALCS PROVIDED SHOWAN R- VALUE OF 1586
 FOR INTERIOR CONCRETE WALL ?? PLEASE CLARIFY, ALSO
 COMPLETE THE INFORMATION IN THE TOP BOX
 (BUILDER,PERMITTING OFFICE,PERMIT # AND JURISDICTION
 #)
  
 PLEASE NOTE THAT ALL FEES AND A NOTICE OF COMMENCEMENT
 WILL BE DUE BEFORE A PERMIT CAN BE ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716