2007-06-19 10:50:04 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| 1. SHEET D-1 PLUMBING RISER: |
| 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE |
| BUILDING OFFICIAL. |
| NOTE: THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN. PLEASE CORRECT OR CLARIFY THE |
| FOLLOWING FOR THE RESUBMITTAL. |
| A} 1ST FLOOR KITCHEN SINK DOES NOT REFLECT THE |
| FLOOR PLAN AND PLEASE ADD THE DISHWASHER DRAIN PER |
| 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE |
| INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF THE |
| KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD |
| WASTE GRINDER. THE |
| KITCHEN SINK APPEARS TO BE LOCATED IN AN ISLAND, IF SO |
| PLEASE DELETE THE 2" VENT THROUGH ROOF AND ADD AN AIR |
| ADMITTANCE VALVE PER 917.3. |
| B} 1ST FLOOR BATH #4, THE LAV AND TUB DO NOT |
| REFLECT THE FLOOR PLAN. |
| C} 2ND FLOOR BATH #1, THE TUB, LAV, AND SHOWER DO |
| NOT REFLECT THE FLOOR PLAN. |
| D} 2ND FLOOR LAUNDRY, THE LAUNDRY TRAY IS MISSING |
| FROM THE RISER DIAGRAM. PLEASE BE AWARE THAT THE |
| MINIMUM SIZE REQUIRED TRAP AND STANDPIPE FOR THE |
| WASHING MACHINE IS TWO INCH (2") PER 406.3 AND THAT YOU |
| ARE INDICATING A THREE INCH TRAP BUT NO STANDPIPE. |
| PLEASE INDICATE THE STANDPIPE FOR THE WASHING MACHINE |
| AND PLEASE CLARIFY THAT IT IS YOUR INTENT TO USE A |
| THREE INCH (3") TRAP ON THE RESUBMITTAL. |
| E} 2ND FLOOR BATH #2, THE LAV AND TUB DO NOT |
| REFLECT THE FLOOR PLAN. |
| F} 2ND FLOOR BATH #3, THE LAV AND TUB DO NOT |
| REFLECT THE FLOOR PLAN. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |