Plan Review Notes
Plan Review Notes For Permit 07050962
Permit Number 07050962
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-19 10:50:04DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SHEET D-1 PLUMBING RISER:
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRECT OR CLARIFY THE
 FOLLOWING FOR THE RESUBMITTAL.
 A} 1ST FLOOR KITCHEN SINK DOES NOT REFLECT THE
 FLOOR PLAN AND PLEASE ADD THE DISHWASHER DRAIN PER
 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE
 INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF THE
 KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER. THE
 KITCHEN SINK APPEARS TO BE LOCATED IN AN ISLAND, IF SO
 PLEASE DELETE THE 2" VENT THROUGH ROOF AND ADD AN AIR
 ADMITTANCE VALVE PER 917.3.
 B} 1ST FLOOR BATH #4, THE LAV AND TUB DO NOT
 REFLECT THE FLOOR PLAN.
 C} 2ND FLOOR BATH #1, THE TUB, LAV, AND SHOWER DO
 NOT REFLECT THE FLOOR PLAN.
 D} 2ND FLOOR LAUNDRY, THE LAUNDRY TRAY IS MISSING
 FROM THE RISER DIAGRAM. PLEASE BE AWARE THAT THE
 MINIMUM SIZE REQUIRED TRAP AND STANDPIPE FOR THE
 WASHING MACHINE IS TWO INCH (2") PER 406.3 AND THAT YOU
 ARE INDICATING A THREE INCH TRAP BUT NO STANDPIPE.
 PLEASE INDICATE THE STANDPIPE FOR THE WASHING MACHINE
 AND PLEASE CLARIFY THAT IT IS YOUR INTENT TO USE A
 THREE INCH (3") TRAP ON THE RESUBMITTAL.
 E} 2ND FLOOR BATH #2, THE LAV AND TUB DO NOT
 REFLECT THE FLOOR PLAN.
 F} 2ND FLOOR BATH #3, THE LAV AND TUB DO NOT
 REFLECT THE FLOOR PLAN.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721