Plan Review Notes For Permit 07050962 |
Permit Number |
07050962 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-06-06 12:40:54 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | 2} PER 110.9 AND 110.10: OBTAIN THE | | AVAILABLE FAULT CURRENT AT THE UTILITY | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | INDICATE THE AIC RATING FOR THE | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | THE AVAILABLE FAULT. | | | | 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1) | | AND 210.52 (A) (2).SEE BEDROOMS #3 AN 4. | | | | 4} SMOKE DETECTORS ARE REQUIRED TO BE INTERCONNECTED | | PER R313.1 FBC, 11.8.2 NFPA-72. BEDROOMS 2 AND 3 NEED. | | | | 5} THE AHU LOADS ON THE PANEL SCEDULE AND IN THE | | CALCULATIONS DO NOT CORRELATE. ALSO 125% SHOULD NOT BE | | USED IN THE CALCULATION FOR THE HEAT. SEE ARTICLE 220. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|