Plan Review Notes
Plan Review Notes For Permit 07050962
Permit Number 07050962
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-06 12:40:54 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2).SEE BEDROOMS #3 AN 4.
  
 4} SMOKE DETECTORS ARE REQUIRED TO BE INTERCONNECTED
 PER R313.1 FBC, 11.8.2 NFPA-72. BEDROOMS 2 AND 3 NEED.
  
 5} THE AHU LOADS ON THE PANEL SCEDULE AND IN THE
 CALCULATIONS DO NOT CORRELATE. ALSO 125% SHOULD NOT BE
 USED IN THE CALCULATION FOR THE HEAT. SEE ARTICLE 220.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.