2008-06-04 11:26:13 | 439 NORTHWOOD RD, LOT 261 07050952 |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 07050952 |
| ADD: 439 NORTHWOOD RD |
| CONT: KDN CONSTRUCTION SERVICES, LLC |
| TEL: (561)662-1002 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RDREVIEW |
| ACTION: DENIED |
| |
| 1)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) FIXED WINDOWS- PLANS INDICATE THE USE OF FIXED |
| WINDOWS WHERE AS THE CONTRACTOR HAS SUPPLIED APPROVALS |
| FOR CASEMENT TYPW WINDOWS, PLEASE SUBMIT THE CORRECT |
| PRODUCT APPROVALS. |
| |
| B) MONIER ROOF TILE FL560-R2LIST THE PRODUCT APPROVAL |
| IS FILED UNDER THE EVALUATION ENTITY AS A ICC |
| EVALUATION SERVICE OR A ICC REPORT. |
| TWO REOPRTS ARE LISTED PLEASE PROVIDE DOCUMENTATION AS |
| TOO WHICH OF THESE REPORTS WILL BE INCORPORATED INTO |
| THE SCOPE OF WORK FOR THIS PROJECT. |
| ESR-1384 |
| ESR-1647 |
| |
| C) FLAT ROOFS: A GAF REPORT AND NOA WAS SUBMITTED BUT |
| THE PAGES 10-20 THE SUB SYSTEMS WERE NOT CIRCLED OR |
| HIGHLIGHTED AS TO WHICH SYSTEM WAS TO BE INSTALLED |
| WWITH ASSOCIATED PRESSURES. |
| IN ALL CASES THE PRESSURES ARE LOW FOR ZONES 2 & 3 AND |
| WILL NEED ENHANCED FASTENING. PLEASE PROVIDERAS |
| CALCULATION FOR ZONES 2 & 3. |
| |
| 2)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 3)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 4) SHEET 4 PARAPET EXTENSION INDICATES THE USE OF 22 |
| GAUGE METAL STUDS. 22 GAUGE METAL STUDS ARE |
| NON-STRUCTURAL STUDS, FOR INTERIOR USE OF DRYWALL ONLY. |
| STRUCTURAL STUDS CAN START WITH A 20 GAUGE- STRUCTURAL |
| GAUGE OR HEAVIER SUCH AS 18 GAUGE STUD. TABLE 2508.1/ |
| ASTM C1007 LOAD BEARING STUDS. |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |